Instruction Manual
Pulsar Plus Controller Family
Issue 7 December 2011 124
System Inputs/Outputs Specifications
Item
Specification
SELV
All input and output connections comply with SELV requirements.
Connections - Ports
CAUTION
Intra-building ports of the equipment or subassembly
• are suitable for connection only to shielded intra-building or
unexposed wiring or cabling grounded at both ends.
• MUST NOT be metallically connected to interfaces which
connect to the OSP or its wiring.
These interfaces are designed for use as intra-building interfaces only
(Type 2 or Type 4 ports as described in GR-1089-CORE, Issue 5) and
require isolation from the exposed OSP cabling.
The addition of Primary Protectors is not sufficient protection.
All controller ports are intra-building except the phone port of the
BSM6 Modem.
Alarm and Control Inputs
(J3) 10-pin connector 2 control and 5 alarm inputs and returns;
(J1) 6-pin connector for 4 basic plant inputs
Alarm Contact Outputs
10 User configurable Form-C Outputs;
(J4) 20-pin connector for 10 individual alarm output contacts;
Wire size: 28-16 AWG stranded or solid
Alarm Contact Ratings 60 VDC, 0.5A
Plant Voltage Measurement
Accuracy 0 to 50°C
-40 to 85°C
Resolution
±0.05% of full scale + 1 count
48V Systems: ±40 mV; 24V Systems ±25 mV
±0.1% of full scale + 1 count)
48V Systems: ±70 mV; 24V Systems ±40 mV
0.01V
Plant Current Measurement
Accuracy 0 to 50°C
-40 to 85°C
Resolution
±0.5% of full scale
±1.25% of full scale
1A
Temperature Measurement
One-Wire Probe
Accuracy -5 to +55°C
-40 to +85°C
Resolution
±1°C
±3°C
0.1°C