Instruction Manual
Pulsar Plus Controller Family
Issue 7 December 2011 142
Table 47 T1.317 User Login Related commands
obj,attr Description sta cha ope type Range of Values
x,ide Identifier
text USR01-USR14, ADM1
x,des Description
text User Account 1-14
Administrator Account
x,pwd Password
text 15 characters
x,usr User name
text 15 characters
x,lvl Security level
text “USER”, “SUPER-USER”,
“ADMINISTRATOR”
Table 48 T1.317 DC Plant Related Commands
obj,attr description sta cha ope type Range of Values
dc1,ide Description
text DC1
dc1,des Description
text DC Plant 1
dc1,typ Plant Type
number 48V, 24V
dc1,vdc Plant voltage
number dd.dd V
dc1,adc Plant load current
number ddd.d A
dc1,cap Total installed rectifier capacity
number ddd.d A
dc1,olcap Total on-line rectifier capacity
number ddd.d A
dc1,trd Plant total rectifier drain
number ddd.d A
dc1,sht Centralized plant shunt type
Text “NONE”, ”BATTERY”, ”LOAD”
dc1,sha Centralized plant shunt size
Number 0=disabled 1-9999
dc1,stt Plant state
text “FLOAT”, “BOOST”
dc1,bod Battery on discharge
number 0=on discharge 1=not on
discharge
dc1,rss Rectifier restart
number 0=no action 1=restart
dc1,rsq Rectifier sequencing
number 0=disable 1=enable
dc1,ron User Group TR request
Number 0-3 LSB = User, MSB=PBT
dc1,rot All Rectifier On Threshold
number 20-25or 40-50 volts
dc1,nst Number of battery strings
number 1-70
dc1,cps Number of Cells per String
number 1-75 (24V plant) or 24 (48V plant)
dc1,bty Battery type
Text See battery type definitions
default (OPE causes battery
defaults to be loaded)
dc1,isd Imminent shutdown enable
number 0=disable 1=enable
dc1,rtm Actual reserve time
text Low Current-Batt current too low
High Current-Batt current too high
dd.d (in hours)
dc1,scap String capacity
number
dc1,mls All load shunts monitored
number 0=disable 1=enable
Table 49 T1.317 Alarms With Two Thresholds Related Command
obj,attr Description sta cha ope type Range of Values
objid,ide Identifier
text see below
objid,des Description
text see below
objid,fds Front Panel Description
text see below
objid,ast Alarm state
number 0=not active 1=active
objid,led LED
text BD,AC,DC,””
objid,sev Alarm severity
text CRIT, MAJ, MIN, WRN, RO
objid,fth Alarm boost threshold
number see below
objid,bth Alarm float threshold
number see below