Instruction Manual
Pulsar Plus Controller Family
Issue 7 December 2011 143
objid,acc Contact Closure
text R1,R2,R3,R4,R5,R6,R7,””
objid,dly Notify Delay
number 0-540 seconds
objid,noo Notify On Occur
number 0=no 1=yes
objid,nor Notify On Retire
number 0=no 1=yes
objid,nag NAG On Occur
number 0=no 1=yes
objid,dst Notify Destination
text “”, P1, P2, P3, P4, E1, E2, E3, E4,
S1, S2, S3, S4
objid Description Float Threshold Boost Threshold
bda1 Battery On Discharge 23-28 V
or 46-55 V
23-28 V
or 46-55 V
hfv1 High voltage 24.75-29.75 V
or 50-60 V
25.75-31.75 V
or 52-60 V
hva1 Very high voltage 24.75-29.75 V
or 50-60 V
25.75-31.75 V
or 52-60 V
Table 50 T1.317 Alarms With One Threshold Related Command
obj,attr Description sta cha ope type Range of Values
objid,ide Identifier
text see below
objid,des Description
text see below
objid,fds Front Panel Description
text see below
objid,ast Alarm state
number 0=not active 1=active
objid,sev Alarm severity
text CRIT, MAJ, MIN, WRN, RO
objid,thr Alarm threshold
number number
objid,led LED
text BD,AC,DC,””
objid,acc Contact Closure
text R1,R2,R3,R4,R5,R6,R7,””
objid,dly Notify Delay
number 0-540 seconds
objid,noo Notify On Occur
number 0=no 1=yes
objid,nor Notify On Retire
number 0=no 1=yes
objid,nag NAG On Occur
number 0=no 1=yes
objid,dst Notify Destination
text “”, P1, P2, P3, P4, E1, E2, E3, E4,
S1, S2, S3, S4
objid Description Threshold
amth1 High ambient temp 30-75C
amtl1 Low ambient temp -40-10C
btha1 High battery temperature 30-85C
mrfa1 Multiple Rectifier Fail 2-88
mman1 Multiple Manual Off 2-88
rrtl1 Real-time reserve low 0-100hrs
rtl1 Reserve time low 0-100hrs
macf1 Multiple AC Fail 2-88
rls1 Redundancy Loss 1-87
cmfa1 Multiple Converter Fail 2-16
chva1 Converter Very High Output Voltage 25-30V
50-60V
chfv1 Converter High Output Voltage 24-30V
48-60V
cvla1 Converter Very Low Output Voltage 20 - 27V
40 - 54V
crl1 Converter redundancy loss 1-16
vla1
Very low voltage
20-25.5 V
or 40-51 V