Table 51 T1.317 Alarms With No Threshold Related Command
obj,attr Description sta cha ope type Range of Values
objid,ide Identifier
text see below
objid,des Description
text see below
objid,fds Front Panel Description
text see below
objid,ast Alarm state
number 0=not active 1=active
objid,sev Alarm severity
text CRIT, MAJ, MIN, WRN, RO
objid,led LED
text BD,AC,DC,””
objid,acc Contact Closure
text R1,R2,R3,R4,R5,R6,R7,””
objid,dly Notify Delay
number 0-540 seconds
objid,noo Notify On Occur
number 0=no 1=yes
objid,nor Notify On Retire
number 0=no 1=yes
objid,nag NAG On Occur
number 0=no 1=yes
objid,dst Notify Destination
text “”, P1, P2, P3, P4, E1, E2, E3, E4,
S1, S2, S3, S4
obj Description
aac1 ACO Active
acf1 AC fail
amj1 Auxiliary Fuse Major
ata1 Alarm Test Active
atb1 Alarm Test Aborted
aux1 Auxiliary alarm 1
aux2 Auxiliary alarm 2
aux3 Auxiliary alarm 3
aux4 Auxiliary alarm 4
aux5 Auxiliary alarm 5
aux6 Auxiliary alarm 6
bbl1 Memory Backup Battery Low
bfa1 Battery Test Failed
bta1 Battery test active
cch1 Configuration Changed
cdid1 Converter ID Conflict
cfa1 Converter Fail
clc1 Clock Changed
clm1 Rectifier Current Limit
cma1 Minor Communication Fail Alarm
cnf1 LVBD 1 Failed
cnf2 LVLD 1 Failed
cnf3 LVLD 2 Failed
cnf4 LVLD 3 Failed
cno1 LVBD 1 Open
cno2 LVLD 1 Open
cno3 LVLD 2 Open
cno4 LVLD 3 Open
cof1 Queue Overflow
cor1 Number Did Not Respond
did1 ID Conflict
epo1 Emergency power (battery) off
epr1 External Password Reset
exl1 Excessive Login Attempts
faj1 External 24V Fuse Major