Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 146
Table 53 T1.317 Rectifiers Related Commands
obj,attr Description sta cha ope type Range of Values
gsr,adc DC Current (VI, VIR)
number number A
gsr,vdc DC Voltage
number number V
gsr,stt Individual rectifier state
text ON*, OFF, STANDBY*,
VACANT*, MISSING
gsr,cap Capacity
number number A
gsr,tmp Temperature
number number F or C
gsr,seq Use In Sequence Enable
number 0=no 1=yes
gsr,rfa Rectifier Fail
number 0=inactive 1=active
gsr,acf AC Fail
number 0=inactive 1=active
gsr,man Standby or Manual Off
number 0=inactive 1=active
gsr,did ID Conflict
number 0=inactive 1=active
gsr,clm Current Limit
number 0=inactive 1=active
gsr,rcf Communication Fail
number 0=inactive 1=active
gsr,rfn Fan fail
number 0=inactive 1=active
s stands for shelf number (1 to 6)
r stands for rectifier number (1 to 7)
* The user may only set the state to ON, STANDBY, or VACANT
Table 54 T1.317 Converter Plant Related Commands
obj,attr Description sta cha ope type Range of Values
cp1,des Description
Text Converter Plant 1
cp1,typ Converter output type
Text 24V or 48V
cp1,vdc DC Voltage
Number Number in volts
cp1,adc DC Current
Number Number in amps
cp1,cap Installed capacity
Number Number in amps
cp1,olcap Online capacity
Number Number in amps
cp1,vsp Voltage Set-Point
Number 23-28V or 46-57V
cp1,vsd Internal high voltage shutdown
Number 25-30V or 50-60V
cp1,dth Low Voltage Discon Threshold
Number 20-25V or 40-50V
cp1,rth Low Voltage Recon Threshold
Number 22-27V or 44-54V
cp1,lvd Low Voltage Disconnect Enable
Number 0=disabled 1=enabled
cp1,rss Converter restart
number 1=restart
cp1,rme Redundancy monitor enable
number 0=disable,1=enable
Cp1,rof Remote standby enable
number 0=disable,1=enable