Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 147
Table 55 T1.317 DC Converter Related Commands
obj,attr Description sta cha ope type Range of Values
csr,des Description
Text DC Converter sr
csr,typ Type
Text 10 chars
csr,sn Serial number
Text Serial number
csr,adc DC Current
Number Number in amps
csr,cap Capacity
Number Number in amps
csr,stt State
Text ON*, OFF, STANDBY*,
MISSING, VACANT*
ON qualifiers LIM
OFF qualifiers LVD, -INF, -
TA, -HVSD, -FAN
csr,cfa Converter Fail
Number 0=inactive 1=active
csr,did ID Conflict
Number 0=inactive 1=active
csr,ccf Communication Fail
Number 0=inactive 1=active
s stands for shelf number (0 or 1)
r stands for converter number (1 thru 6)
* The user may only set the state to ON, STANDBY, or VACANT
Table 56 T1.317 Battery Reserve Management Related Commands
obj,attr Description sta cha ope type Range of Values
br1,des Description
Text Battery Reserve 1
br1,adc Total battery current
number d A (+ for discharge, - for
charge)
br1,hbt Highest battery temperature
number
dd °C
br1,cap Installed battery capacity
number ddddd AH
br1,olcap
On-line battery capacity
number
ddddd AH
br1,btr Discharge test results
result,reserve,load text
result is one of the following:
COMPLETED
CHECK BATTERY
INTERRUPTED
ACTIVE
NOT RUN
reserve is hours calculate by
last complete test
load is load at beginning of
test
br1,tth High Temperature Threshold
Number
30-90
°
C or 86-194
°
C
br1,cle Current Limit Enable
number 0=disable 1=enable
br1,clt Current Limit Threshold
number 5-1000A
br1,cev Battery string end of discharge V
Number 19.25-22.75V
or 40.25-43.75V
br1,bts Battery Test State
number 0=inactive 1=active
br1,mtt Manual test type
text DISABLED, 20%, TIMED
br1,tev Manual test alarm voltage
number 21-27V or 36-48 V
br1,tmd Manual test duration
number 0.1-99.9 hours
br1,bte Auto test type
text DISABLED, 20%, TIMED
br1,btv Battery test rectifier voltage
number 21-26 V or 42-52 V
br1,ath Auto test start hour
number 0-23
br1,tin
Auto test interval
number
1-18 months
br1,atw Auto test min hours after BD
number 0-240 hours
br1,atd Auto test date
date dd-mmm-yy