Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 148
Table 56 T1.317 Battery Reserve Management Related Commands
obj,attr Description sta cha ope type Range of Values
br1,nvm Number of mid-cell V present
d
br1,ntm Number of temperatures present
d
br1,scd Battery voltage imbalance
detection enable
number 0=disable,1=enable
(Automatically enabled
when mid cell V monitor
present)
br1,scv Battery imbalance threshold
number 1.5-3.0V
Table 57 T1.317 Battery Type Definition Related Commands
obj,attr Description sta cha ope type Range of Values
btnn,des Description
Text Battery Configuration 1
btnn,bty Battery Type
Text Up to 14 characters
btnn,btc Battery Class
Text FLOODED, SEALED, NICD,
LI_LMP, LI_ELITE
btnn,cap Capacity
Number number
Where n stands for battery type number (1 thru 25)
Table 58 T1.317 Boost Management Related Commands
obj,attr Description sta cha ope type Range of Values
bs1,ide Identifier
Text BS1
bs1,des Description
Text Boost Control 1
bs1,stt State
Text QRCT, MANUAL, BTP, TIMED
AU-TO, OFF
bs1,atm Auto Mode
Text OFF, QRCT, TIMED
bs1,tmd
Timed Manual Duration
Number
1-80 hours
bs1,amf Auto Multiplication Factor
Number 0.1-9
bs1,cta Current Term Current Thresh
Number 1-999A
Table 59 T1.317 Disconnect Contactor Control Related Commands
obj,attr Description sta cha ope type Range of Values
cnx,ide Identifier
number CN1, CN2, CN3, CN4
cnx,des Description
number Contactor 1
cnx,stt Status
text NONE, DISCON, CONNECT,
FAILED
cnx,ena Control enable
0=disable,1=enable
cnx,dth Disconnect threshold
number 19-25V or 39-50V
cnx,ddy Disconnect delay
number 0-300 minutes
cnx,dam Disconnect automode
text 0=“NONE”
1=“VOLTAGE
2= “VOLTAGE+TIME”
cnx,dtm Disconnect remaining time
number >0 means going to
disconnect
cnx,rth Reconnect threshold
number 19.5-27V or 39-55V
cnx,rdy Reconnect delay
number 0-300 seconds
cnx,ram Reconnect automode
text 0=“NONE”
1=“VOLTAGE
2=“VOLTAGE+TIME
cnx 4,rtm Reconnect remaining time
number >0 means going to reconnect
The contactors are identified as follows: