Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 149
CN1 = Battery Disconnect (LVBD1)
CN2 = Load 1 Disconnect (LVLD1)
CN3 = Load 2 Disconnect (LVLD2)
CN4 = Load 3 Disconnect (LVLD3)
Table 60 T1.317 Distribution Current Monitor Related Commands
obj,attr Description sta cha ope type Range of Values
dcmxx,ide Identifier
number DCMC1 is the plant shunt
DCM01-DCM08
dcmxx,des Description
number Contactor 1
dcmxx,stt State
text NONE
MISSING
PRESENT
dcmxx,typ Shunt Type
text NONE
LOAD
BATTERY
dcmxx,val Reading
number ddd.d Amps
dcmxx,sha Shunt amp rating
number 0-9999 Amps
The shunt type defaults are as follows:
DCMC1 = Battery
DCM01 = Battery
DCM02-DCM08 = Load
Table 61 T1.317 Distribution Contactor Interface Related Commands
obj,attr Description sta cha ope type Range of Values
dcnxx,ide Identifier
number DCN01-DCN06
dcnxx,des Description
number Contactor 1
dcnxx,stt State
text NONE
MISSING
OPEN
CLOSED
dcnxx,typ Contactor interface type
text NONE, CN1, CN2, CN3, or
CN4
The contactor interface type defaults are as follows:
DCN01 = CN1
DCN02 = CN2
DCN03 = CN3
DCN04-DCN08 = CN4
Table 62 T1.317 Slope Thermal Compensation Related Commands
obj,attr Description sta cha ope type Range of Values
sc1,ide Identifier
Text SC1
sc1,des Description
Text Slope Thermal Comp
sc1,stt State
number 0=disable 1=enable
sc1,rve Raise Voltage Enable
number 0=disable 1=enable
sc1,ltt Lower Temperature Threshold
number
-5-20°C or 23-68°F
sc1,ntt Nominal Temperature Threshold
number
15-30°C or 59-86°F
sc1,utt Upper Temperature Threshold
number
30-55°C or 86-131°F
sc1,spt Step Temperature
number
45-85°C or 113-185°F
sc1,lsp Low temperature slope
number
1-10mV/°C per cell
sc1,usp Upper temperature slope
number
1-10mV/°C per cell