Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 150
Table 63 T1.317 Input Management Related Commands
obj,attr Description sta cha ope type Range of Values
inmnn,stt Input state
text 0=not alarming 1=alarming
inmnn,typ Input alarm type
text "" no alarm, for in006, this value
allows the input to be used
for either group standby or
PBT. Polarity is ignored.
"FAN1" - drives FAN1 alarm
"FAN2" drives FAN2 alarm
"FAJ1" drives FAJ1 alarm
"FAJ2" drives FAJ2 alarm
"OSA1" drives OSA1 alarm
"AMJ1" drives AMJ1 alarm, not
valid for NE872 or other LVD
card inputs.
"AUX1" drives AUX1 alarm
"AUX2" drives AUX2 alarm
“AUX3" drives AUX3 alarm
“AUX4" drives AUX4 alarm
“AUX5" drives AUX5 alarm
“AUX6" drives AUX6 alarm
"REMLVD" Active signal opens
battery contactors for built-in
plant input, or for LVD inputs,
it opens the contactor on the
card where the signal is
active.
inmnn,pol Input alarming state
text CLOSED, OPEN
where: m is the distribution interface module ID from 1 to 4
nn is the input number from 01 to the number of inputs supported by the distribution interface
module
Built-in plant inputs
Object Signal Name Default Description
In001 FAJ1 Fuse Alarm Major 24V
In002 FAJ2 Fuse Alarm Major 48V
In003
AUX_PMJ
Auxiliary Major Alarm
In004 OS_BATT Open String
In005 EPO_IN Emergency Power Off
In006 PBT_IN Group Standby/PBT
In007 AUX1_IN Air Conditioner Fail
In008
AUX2_IN
Door Open
In009 AUX3_IN High External Ambient
In010
AUX4_IN
Low External Ambient
Table 64 T1.317 Call-Out Manager Related Commands
obj,attr Description sta cha ope type Range of Values
cm1,des Description
text 30 char (Call-Out Manager)
cm1,ngi NAG Interval
Number 15 to 60 minutes