Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 156
Additional T1.317 Commands And Samples
ala Report Active Alarms
Syntax:
ala
Description
This command reports all the active alarm conditions in the plant. One alarm message is listed
per line in the report. The table below lists the default alarm messages. Note that if user
changes the severity of the alarm, the corresponding change will show up in the alarm
message. However, alarm conditions with the RO severity will not be displayed, the rec
command, discussed later, must be used.
Alarm Message
MAJ, Multiple Rectifier Fail
MAJ, Multiple AC Fail
MAJ, Battery On Discharge
MAJ, High Voltage
MAJ, Sense Fuse
MAJ, Fuse Major
MAJ, Auxiliary Major
MAJ, Contactor 1 Open
MAJ, Contactor 1 Fail
MAJ, Major Communication Fail
MAJ, High Battery Current Shutdown
MAJ, Shorted Cell Detected
MAJ, Imminent Low V Shutdown
MAJ, Open String
MIN, Rectifier Fail
MIN, AC Fail
MIN, Thermal Probe Fail
MIN, Battery High Temp
MIN, Rect Redundancy Loss
MIN, High Battery Current
MIN, Minor Communication Fail
MIN, Circuit Pack Failure
MIN, Mid-cell V Monitor Fail
If no alarms are active “NO ACTIVE ALARMS” is reported.
bye Log-off
Syntax:
bye
Description
This command is used to terminate the session.