Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 157
cha Change Value
Syntax:
cha obj,attr=value
where: obj,attr is an object-attribute pair. For example, ps1,sid.
Description
This command is used to change system configuration parameters. Examples are listed below
to illustrate how this command works.
cha ps1,sid="My Plant"Change the site id to My Plant
cha p1,phn="123456789"Change the primary phone number to 123456789
You must be logged in as a super-user to use this command.
cle Clear All Latched Events
Syntax:
cle
Description
This command is used to clear latched events. These events include communication failures,
missing rectifiers, missing thermal probes, missing voltage monitoring module, distribution
fuses, and loss of redundancy alarm.
You must be logged in as a super-user to use this command.
his Report Alarm History
Syntax:
his
Description
Syntaxhis
where: obj,attr is an object-attribute pair as defined in the following:
sum dc1,adc- report plant load current statistics
sum br1,hbt- report highest battery temperature statistics
his Report Boost History
Syntax:
his bs1,stt
Description
This command reports the boost history in the following format:
sum bs1,stt
30-MAY-03,15:11:12,RESUMED,COMPLETED,78
30-MAY-03,12:03:34,AUTO,DISCHARGE,14
**
This report gives the start date, start time, start reason, stop reason, and boost duration in
minutes. The start reasons are:
MANUALBoost initiated by user
AUTOBoost started automatically after a battery discharge
RESUMEDBoost resumed after being suspended by a discharge
The stop reasons are:
COMPLETEDBoost completed normally
TIMEOUTBoost timed out before completing
DISCHARGEBoost suspended because of a battery discharge
CANCELEDBoost canceled by user
ALARMBoost cancelled by an alarm condition