Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 172
Table D-1 Standard Configuration Item Defaults
Factory Default
Factory 24V
Rectifier
Default
Factory 48V
Rectifier
Default
Category Description Range Factory Factory 24V Factory 48V obj,attr
Controller
Site ID ≤ 20 characters "" PS1,SID
Site Description ≤ 55 characters "" PS1,SDE
Controller Description Plant Description "NE843A" PS1,DES
System Description ≤ 55 characters "Infinity NE" PS1,SYS
Plant Description Plant Description "H569-2448" DC1,DES
Plant Voltage Type 24V or 48V "24V" "48V" DC1,TYP
Automatic Daylight Savings Feature
1=Enabled
0=Disabled
1 PS1,DLS
Display Contrast 0 to 100% 50 PS1,DCT
Temperature Display Units C or F "C" PS1,TUN
Date Format "MM/DD/YYYY" PS1,DTF
Time Format 12 or 24 12 PS1,TMF
Front Panel Configuration
1=Enabled
0=Disabled
1 PS1,FPC
Remote rectifier Off
1=Enabled
0=Disabled
0 PS1,RRF
Emergency Power-off Enable
1=Enabled
0=Disabled
1 PS1,POE
User Name Login Enable
1=Enabled
0=Disabled
0 PS1,USR
Front Panel PIN enable
1=Enabled
0=Disabled
0 PS1,FPE
Front Panel Pin Default Four digits 0-9 "0000" PS1,FPP
Front Panel PIN timeout 1 to 120 minutes 30 PS1,FPT
Daylight Saving Start
mon:wk:dow:min
mon:-1:dom:min
"3:2:0:120" PS1,DSS
Daylight Saving End
mon:wk:dow:min
mon:-1:dom:min
"11:1:0:120" PS1,DSE
Uninstall Equipment Timeout 0 to 60s 15 PS1,UET
Controller Ambient Temperature
High
35 to 75
c
C 75 AMTH1,THR
Controller Ambient Temperature
Low
-40 to 10 C -40 AMTL1,THR
Critical Equals Major
1=Enabled
0=Disabled
1 PS1,CEM
User Password "lineage" PAS U,
Super-user Password "super-user" PAS S,
Administrator Password "administrator" PAS A,
Low Voltage
Disconnects
Battery Disconnect Control Mode
0=none, 1=voltage
2=voltage/time
1 CN1,DAM
Battery Disconnect 1
Battery Disconnect Time Delay 0 to 300 minutes 0 CN1,DDY
Battery Reconnect Control Mode
0=none, 1=voltage
2=voltage/time
1 CN1,RAM
Battery Reconnect Time Delay 0 to 300 sec 0 CN1,RDY
Battery Disconnect Description <=32 Chars "LVBD1" CN1,DES
Battery Disconnect Open
Description
<=32 Chars "LVBD1 Open" CNO1,DES
Battery Disconnect Open Front
Panel Description
<=32 Chars "LVBD1 Open" CNO1,FDS
Battery Disconnect Failed
Description
<=32 Chars "LVBD1 Failed" CNF1,DES
Battery Disconnect Failed Front
Panel Description
<=32 Chars "LVBD1 Failed" CNF1,FDS
Load Disconnect 1
Load 1 Disconnect
1=Enabled
0=Disabled
1 CN2,ENA