Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 173
Table D-1 Standard Configuration Item Defaults
Factory Default
Factory 24V
Rectifier
Default
Factory 48V
Rectifier
Default
Category Description Range Factory Factory 24V Factory 48V obj,attr
Load 1 Disconnect Control Mode
0=none, 1=voltage
2=voltage/time
1 CN2,DAM
Load 1 Disconnect Voltage
19.5 to 25V
-39.0 to -50V
21.00 42.00 CN2,DTH
Load 1 Disconnect Time Delay 0 to 300 minutes 0 CN2,DDY
Load 1 Reconnect Control Mode
0=none, 1=voltage
2=voltage/time
1 CN2,RAM
Load 1 Reconnect Voltage
19.5 to 27
-39.0 to -55.0V
22.00 44.00 CN2,RTH
Load 1 Reconnect Time Delay 0 to 300 sec 0 CN2,RDY
Load 1 Disconnect Description <=32 Chars "LVLD1" CN2,DES
Load 1 Disconnect Open Description <=32 Chars "LVLD1 Open" CNO2,DES
Load 1 Disconnect Open Front Panel
Description
<=32 Chars "LVLD1 Open" CNO2,FDS
Load 1 Disconnect Failed
Description
<=32 Chars "LVLD1 Failed" CNF2,DES
Load 1 Disconnect Failed Front
Panel Description
<=32 Chars "LVLD1 Failed" CNF2,FDS
Load Disconnect 2
LV Load 2 Disconnect
1=Enabled
0=Disabled
0 CN3,ENA
LV Load 2 Disconnect Control Mode
0=none, 1=voltage
2=voltage/time
1 CN3,DAM
LV Load 2 Disconnect Voltage
19.5 to 25V
-39.0 to -50V
21.00 42.00 CN3,DTH
LV Load 2 Disconnect Time Delay 0 to 300 minutes 0 CN3,DDY
LV Load 2 Reconnect Control Mode
0=none, 1=voltage
2=voltage/time
1 CN3,RAM
LV Load 2 Reconnect Voltage
19.5 to 27
-39.0 to -55.0V
22.00 44.00 CN3,RTH
LV Load 2 Reconnect Time Delay 0 to 300 sec 0 CN3,RDY
Load 2 Disconnect Description <=32 Chars "LVLD2" CN3,DES
Load 2 Disconnect Open Description <=32 Chars "LVLD2 Open" CNO3,DES
Load 2 Disconnect Open Front Panel
Description
<=32 Chars "LVLD2 Open" CNO3,FDS
Load 2 Disconnect Failed
Description
<=32 Chars "LVLD2 Failed" CNF3,DES
Load 2 Disconnect Failed Front
Panel Description
<=32 Chars "LVLD2 Failed"
CNF3,FDS
Load Disconnect 3
Load 3 Disconnect
1=Enabled
0=Disabled
0 CN4,ENA
Load 3 Disconnect Control Mode
0=none, 1=voltage
2=voltage/time
1 CN4,DAM
Load 3 Disconnect Voltage
19.5 to 25V
-39.0 to -50V
21.00 42.00 CN4,DTH
Load 3 Disconnect Time Delay 0 to 300 minutes 0 CN4,DDY
Load 3 Reconnect Control Mode
0=none, 1=voltage
2=voltage/time
1 CN4,RAM
Load 3 Reconnect Voltage
19.5 to 27
-39.0 to -55.0V
22.00 44.00 CN4,RTH
Load 3 Reconnect Time Delay 0 to 300 sec 0 CN4,RDY
Load 3 Disconnect Description <=32 Chars "LVLD3" CN4,DES
Load 3 Disconnect Open Description <=32 Chars "LVLD3 Open" CNO4,DES
Load 3 Disconnect Open Front Panel
Description
<=32 Chars "LVLD3 Open" CNO4,FDS
Load 3 Disconnect Failed
Description
<=32 Chars "LVLD3 Failed" CNF4,DES
Load 3 Disconnect Failed Front
Panel Description
<=32 Chars "LVLD3 Failed" CNF4,FDS