Table D-1 Standard Configuration Item Defaults
Factory Default
Factory 24V
Rectifier
Default
Factory 48V
Rectifier
Default
Category Description Range Factory Factory 24V Factory 48V obj,attr
Call-Out Parity n,e,o N COP,PRY
Call-Out Stop Bits 1 or 2 1 COP,SBT
Pager ID Delay 0 to 9 seconds 0 COP,DLY
Pager ID up to 25 Characters "" COP,PGR
Pager Message up to 25 Characters "" COP,MSG
Periodic Dial-Out
Phone Number up to 25 Characters "" PSO,PHN
Baudrate
300, 1200, 2400,
4800, 9600, 19200
2400 PSO,BDR
Data Bits 7 or 8 8 PSO,DBT
Parity n,e,o N PSO,PRY
Stop Bits 1 or 2 1 PSO,SBT
Interval
Sunday-Saturday,
Daily, Monthly,
Quarterly, Never
"Never" PO1,INT
Time hh:mm 6:00 PSO,TIM
Command Line 1 <=40 characters "" PSO,CL01
Command Line 2 <=40 characters "" PSO,CL02
Command Line 3 <=40 characters "" PSO,CL03
Command Line 4 <=40 characters "" PSO,CL04
Command Line 5 <=40 characters "" PSO,CL05
Command Line 6 <=40 characters "" PSO,CL06
Command Line 7 <=40 characters "" PSO,CL07
Command Line 8 <=40 characters "" PSO,CL08
Command Line 9 <=40 characters "" PSO,CL09
Command Line 10 <=40 characters "" PSO,CL10
Alarm Email
Notification
IP Address "" COE,ADR
Email Type normal or pager "NORMAL" COE,TYP
Call-Back Security
Call-Back Security Enable
1=Enabled
0=Disabled
0 CBS,STT
Phone Number 1 up to 25 Characters "" CBS,PH1
Baudrate 1
300, 1200, 2400,
4800, 9600, 19200
2400 CBS,BR1
Phone Number 2 up to 25 Characters "" CBS,PH2
Baudrate 2
300, 1200, 2400,
4800, 9600, 19200
2400 CBS,BR2
Phone Number 3 up to 25 Characters "" CBS,PH3
Baudrate 3
300, 1200, 2400,
4800, 9600, 19200
2400 CBS,BR3
Phone Number 4 up to 25 Characters "" CBS,PH4
Baudrate 4
300, 1200, 2400,
4800, 9600, 19200
2400 CBS,BR4
Phone Number 5 up to 25 Characters "" CBS,PH5
Baudrate 5
300, 1200, 2400,
4800, 9600, 19200
2400 CBS,BR5
SNMP Destination
IP Address "0.0.0.0" SND,IP