Table D-2 24V Battery Related Items Defaults
Category Description Range Valve-Reg Flooded Li_ELiTE NiCd Li-LMP obj,attr
Voltage Settings
Float Rectifier High Voltage Shutdown 25 to 30V 29.25 29.25 29.25 29.25 29.25 GM1,FSD
Float High Voltage Major Alarm 25.74 to 31.75V 28.24 28.24 28.24 28.24 28.24 HVA1,FTH
Float High Voltage Minor Alarm 24.75 to 29.75V 27.74 27.74 27.74 27.74 27.74 HFV1,FTH
Float Voltage 21 to 28V 27.24 26.04 27.24 27.20 27.24 GM1,FSP
Float Battery on Discharge Alarm 23 to 28V 25.54 25.00 26.50 25.54 25.54 BDA1,FTH
Very Low Voltage Alarm 20 to 25.5V 23.00 23.00 23.00 23.00 23.00 VLA1,THR
Rectifier On Threshold 20 to 25V 22.00 22.00 22.00 22.00 22.00 DC1,ROT
Battery Disconnect
LV Battery Disconnect
1=Enabled
0=Disabled
1 1 0 1 0 CN1,ENA
LV Battery Disconnect Voltage 19.5 to 25V 21.00 21.00 21.00 21.00 21.00 CN1,DTH
LV Battery Reconnect Voltage 19.5 to 25V 22.20 22.20 22.20 22.20 22.20 CN1,RTH
Batteries
Cells Per String 0-75 12 12 12 12 12 DC1,CPS
String End Of Discharge Voltage 19.25 to 25.35 21.00 21.00 21.00 21.00 21.00 BR1,CEV
Recharge Current Limit Feature
1=Enabled
0=Disabled
0 0 0 0 0 BR1,CLE
Recharge Current Limit Value 5 to 1000A 50 50 25 25 25 BR1,CLT
Boost Maximum Duration 1 to 80 Hours 1 1 1 1 1 BS1,TMD
Voltage Imbalance Detect 1.5V to 3.0V 1.7 1.7 1.7 2.0 1.7 BR1,SCV
High Temperature Disconnect 30 to 90
o
C 75 75 75 75 75 BR1,TTH
High Battery Temperature 30 to 85
o
C 55 55 55 55 85 BTHA1,THR
Battery Slope
Compensation
Slope Thermal Compensation (STC)
1=Enabled
0=Disabled
1 0 0 0 0 SC1,STT
High Temperature Voltage Step Down 45 to 85
o
C 75 75 75 75 75 SC1,SPT
High Temperature Compensation Stop 30 to 55
o
C 55 55 55 55 55 SC1,UTT
High Temperature Decrease Rate
1-10mV/
o
C per
cell
3 3 3 3 3 SC1,USP
Nominal Temperature (No Temp
Comp)
15 to 30
o
C 25 25 25 25 25 SC1,NTT
Low Temperature Compensation
Feature
1=Enabled
0=Disabled
0 0 0 0 0 SC1,RVE
Low Temperature Compensation Stop -5 to 20
o
C 0 0 0 0 0 SC1,LTT
Low Temperature Decrease Rate
1-10mV/
o
C per
cell
3 3 3 3 3 SC1,LSP
Battery Discharge Test
Timed Test Alarm Voltage Threshold 21 to 27V 22.00 22.00 23.00 22.00 22.00 BR1,TEV
Rectifier Voltage During Battery Test 21 to 26V 21.00 21.00 21.00 21.00 21.00 BR1,BTV
Battery Boost
Boost Rectifier High Voltage Shutdown 26 to 30V 29.25 29.25 29.25 29.25 29.25 GM1,BSD
Boost High Voltage Major Alarm 25.75 to 31.75V 28.24 29.00 28.24 28.24 28.24 HVA1,BTH
Boost High Voltage Minor Alarm 25.75 to 31.75V 27.74 28.00 27.74 27.74 27.74 HFV1,BTH
Boost Voltage 22 to 30V 27.24 26.04 27.24 27.20 27.24 GM1,BSP
Boost Battery on Discharge Alarm 23 to 28V 25.54 25.00 26.50 25.54 25.54 BDA1,BTH