Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 189
Table E-2 Alarms, Alarm Relays and LEDs Assignments Phoenix Display
Severity - Relay and Display Additional Relay LED
Description CRIT PMJ PMN WRN RO R1 R2 R3 R4 R5 R6 R7
Object
ID
Incompatible Converter MIN CFA ICC1
Incompatible Rectifier MIN R5 RFA ICR1
Low Battery Temperature RO BTLA1
LV Disconnect Contactor 1 Fail CRIT MAJ LVD CNF1
LV Disconnect Contactor 1 Open CRIT MAJ LVD CNO1
LV Disconnect Contactor 2 Fail CRIT LVD CNF2
LV Disconnect Contactor 2 Open CRIT LVD CNO2
LV Disconnect Contactor 3 Fail MAJ LVD CNF3
LV Disconnect Contactor 3 Open MAJ LVD CNO3
LV Disconnect Contactor 4 Fail MAJ LVD CNF4
LV Disconnect Contactor 4 Open MAJ LVD CNO4
Manual Off MIN MAN1
Multiple AC Fail MAJ R1 ACF MACF1
Multiple Converter Fail MAJ R7 CFA CMFA1
Multiple Manual Off MAJ MMAN1
Multiple Rectifier Fail MAJ R6 RFAM MFA1
No Call-Out Response WRN COR1
No Dial-Out Response WRN POR1
Open String MAJ R3 DFA OSA1
Password At Default RO PFD1
Processor Halt RO PHT1
Program Line Invalid MAJ PGI1
Queue Overflow WRN COF1
Real-Time Reserve Time Low RO RRTL1
Rectifier Current Limit RO CLM1
Rectifier Fail MAJ R5 RFA RFA1
Rectifier Fan Fail MIN R5 RFA RFN1
Rectifier Redundancy Loss MIN LMR RLS1
Reserve Time Low RO RTL1
Ringer External Failure Major MAJ RPXJ1
Ringer External Failure Minor MIN RPXN1
Ringer Fail Major MAJ RPFJ1
Ringer Fail Minor MIN RF1
Ringer Fan Fail MIN RPFF1
Ringer ID Conflict MAJ RCDP1
Ringer Redundancy Loss MIN RPRL1
Self Test Failed MIN STF1
Sense Fuse MIN VSF1
Unconfigured Alarm Destination WRN NNC1
Un-powered Controller (Not configurable) x x x x x x x x x x x
Very High Battery Temperature
MAJ BAT
BTVH1
Very Low Battery Temperature
RO
BTVL1
Very Low Voltage MAJ
BOD,
VLV
VLA1
Voltage Duplicate ID MAJ MDP1