Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 21
Install and Configure Slot/Door-Mount Controllers
Step Action
Jumper
Number
Signal
Name
Table 2 Controller Standard Defaults Door Mounted
Pulsar Plus Display Phoenix Display
1 PCR Power Critical Alarm severity indicator
2 PMJ Power Major Alarm severity indicator
3 PMN Power Minor Alarm severity indicator
4 R1
Battery on Discharge alarm
(BD)
AC/Multiple AC Fail
(ACF, MACF)
5 R2
Very Low Voltage alarm
(VLV)
Battery on Discharge, Battery Test
Active
(BD, BTA)
6 R3
Fuse Alarm
(FAJ1/2/FAN1/2)
Distribution Fuse/CB Alarm, Open
String
(FAJ1/2, FAN1/2, CDFA, AMJ, OSA)
7 R4
AC Fail alarm
(ACF)
High Voltage
(HVA, HFV)
8 R5
Rectifier/Converter Fail
alarm
(RFA/ CFA)
Rectifier Fail, Incompatible
Rectifier
(RFA, RFN, ICR)
9 R6
Multiple Fail alarm
Rectifier/Converter/AC
(MACF/MRFA/
MCFA/MMAN)
Multiple Rectifier Fail
(MRFA/MFA)
10 R7
High Voltage alarm -
Rectifier and Converter
(HVA/HFV/CHVA/CHFV
Converter Fail/Multiple Converter
Fail, Converter Redundancy Loss,
Converter Low Voltage, Converter
High Voltage, Converter ID
Conflict
(CFA, MCFA, CFN, CRL, CVLA,
CHVA, CHFV, CDID)
If your system using the optional ES771 Mid-String Voltage Modules continue with Step 4.
Otherwise go to step 5.