Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 34
Connect to the Controller
Step Action
Table 5 Output Alarm Connector
Pin #
Wire
Color
Signal
Name
Pin #
Wire
Color
Signal
Name
Pulsar Plus Display
Defaults
Phoenix Display
Defaults
1
(BL)
PCR
11
(BL-BK)
PCR_C
Power Critical Alarm
(PCR)
2
(O)
PMJ
12
(O-BK)
PMJ_C
Power Major Alarm
(PMJ)
3
(G)
PMN
13
(G-BK)
PMN_C
Power Minor Alarm
(PMN)
4
(BR)
R1
14
(W-BK)
R1_C
Battery on Discharge
(BD)
AC/Multiple AC Fail
(ACF, MACF)
5
(S)
R2
15
(BK-W)
R2_C
AC/Multiple AC Fail
(ACF/MACF)
Battery on Discharge,
Battery Test Active
(BD, BTA)
6
(BL)
R3
16
(BL-R)
R3_C
Rectifier/Converter Fail
(RFA/MRFA,
CFA/MCFA)
Distribution Fuse/CB Alarm,
Open String
(FAJ1/2, FAN1/2, CDFA, AMJ,
OSA)
7
(O)
R4
17
(R)
R4_C
Very Low Voltage
(VLV)
High Voltage
(HVA, HFV)
8
(G)
R5
18
(R-G)
R5_C
Fuse Alarm - 48V
2
(External FAJ2/FAN2)
Rectifier Fail,
Incompatible Rectifier
(RFA, RFN, ICR)
9
(BR)
R6
19
(R-W)
R6_C
High Voltage
(HV)
Multiple Rectifier Fail
(MRFA)
10
(S)
R7
20
(R-BK)
R7_C
Fuse Alarm - 24V
2
(External FAJ1/FAN1)
Converter Fail/Multiple
Converter Fail, Converter
Redundancy Loss, Converter
Low Voltage, Converter High
Voltage, Converter ID Conflict
(CFA, MCFA, CFN, CRL, CVLA,
CHVA, CHFV, CDID)
1 Configuration jumpers for the alarm outputs have been set to provide an “Open” on alarm
from the factory. See previous sections for changing the alarm contact type at J4.
2
Depending on the system rectifier voltage one of these will be defaulted as a general purpose
output User Relay. Ex: if the system is -48V, then User relay R7 is unassigned and vice versa.