Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 46
Basic Controller Configuration
Step Action
1 Change the battery type to another battery type or specific model.
From the front panel go to Menu
Configuration
Batteries
Type and select a battery model
from the list. If the battery model is unique, select a generic technology class for the installed
battery or use the Craft port to enter a specific battery model. A new model can be entered into
the controller through the use of the web pages at Settings
Battery Types. Note: the present
controller can store 20 specific batteries. One may have to be deleted before adding.
Specific battery models stored in the standard controller:
12A100FT
12A150FT
12IR150/150LP
3A125-33L
3A95-21L
3A95-27L
3A95-33L
6A95-13L
6A95-15L
IR30EC
IR40EC
L54V63FTX
NCX-125
NCX-80
NSB110FT
NSB170FT
NSB60FT
SE48S63
SE48S80
TEL12-105F
Generic Battery technologies:
Valve-Regulated Lead Acid (Valve-Reg)
Flooded Lead Acid (Flooded)
Lithium Metal Polymer (Li-LMP)
Lithium ELiTE (Li-ELiTE)
Nickel-Cadmium (Ni-Cd)