Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 59
Table 10 Status LEDs - Custom Assignable - Phoenix
4
LED
5
Color Alarm Name Condition
ACF Amber AC Fail Alarm A rectifier is reporting AC failure.
RFA Amber
Rectifier Fail
Alarm
A rectifier has failed.
RFAM
(MRFA)
Red
Rectifier Fail
Multiple Alarm
Multiple rectifiers have failed.
HVSD Red
High Voltage
Shutdown Alarm
One or more rectifiers is shutdown due to plant voltage
exceeding the configured threshold.
HVA Red
High Voltage
Alarm
System voltage exceeds the configured threshold.
BOD
(BD)
Red
Battery on
Discharge Alarm
System voltage below configured threshold.
VLV
(LLVA)
Red
Very Low Voltage
Alarm
System voltage below configured threshold.
(USR2) Amber User configurable LED.