Status
Status menus provide an overview of system components, threshold settings, and feature configuration.
Configuration is not possible from here. Status items are also available through the remote port connections
such as the web interface or local craft port using EasyView.
Rectifiers
Table 11 Rectifier Status
Installed Capacity The total installed rectifier capacity in the system. These rectifiers may or may
not have AC applied or be outputting power.
On-line Capacity The total rectifier capacity of rectifiers On-line in the system and able to
produce power. Rectifiers that are running or in Standby are considered to be
On-line. Rectifiers that are in RFA, ACF, etc. are not counted in the On-line
capacity.
Total Output Current The total output current of all rectifiers. This value is also displayed on the
default front panel screen.
Rectifier Monitoring
Each individual rectifier’s DC output current, AC input current, and AC input
voltage
by rectifier number Gmn () is available. “m” represents the shelf
number and “n” represents the rectifier position number in that shelf. The state
of the rectifier is also identified in the () when current is not shown. These
states could be
OFF: Rectifier has been shutdown due to hardware failure (ex RFA, Temp,
HV).
STANDBY: User has inhibited the rectifier's output voltage.
MISSING: An acknowledged rectifier has been removed.
VACANT: Rectifier has not been installed in that position.
Converters
Table 12 Converter Status
Type Provides generic description of the type of converter installed in the system.
The information is of the format “24 to 48“or “48 to 24”.
Voltage Displays the measured value of the secondary (converter) DC output bus. This
value is also displayed on the default front panel screen.
Installed Capacity Provides the total installed converter capacity in the system.
On-line Capacity The total converter capacity of rectifiers On-line in the system and able to
produce power. Converters that have failed are not counted.
Total Output Current The total output current of all converters. This value is also displayed on the
default front panel screen.
Converter Currents The individual converter output currents by converter number (Cmn) are
available. “m” represents the shelf number and “n” represents the rectifier
position number in that shelf.