numbers separated by periods (ddd.ddd.ddd.ddd). Each number, ddd, can be 0
to 255.
DNS
*
Address of the Domain Name Server that translates domain names into IP
addresses. This field is of the format ddd.ddd.ddd.ddd.
Mail Server The address for the computer or equipment within the network that will
manage the controller e-mails. The format for the Gateway address field is a 32-
bit numeric address written as four numbers separated by periods
(ddd.ddd.ddd.ddd). Each number, ddd, can be 0 to 255. If configured as 0.0.0.0,
the controller will use the hostname mail host.
Write Access
This field shows whether the port has bee configured to allow Read/Write
access or Read Only access. Read/Write access is available when the feature has
been enabled.
*
These fields are automatically assigned when using the DHCP server or Client mode of operation.
System Info
Table 19 System Info Status
System Up to 55 characters used to describe the system in which the controller resides.
For example: Infinity NE. Note: The front panel will display only the first 22
characters.
Controller Info Provides software versions running on the controller. These versions include
the versions for the application code, the boot block, the display, the defaults
file, and the web pages.
Date Present Date of the controller on-board real-time clock using the configured
Date format.
Time Present time of the controller on-board real-time clock using the configured
time format.
Ambient
Temperature
Present temperature of the controller on-board temperature sensor displayed
in the configured temperature format.
Control/Operations
The following are the system control and operation functions that can be performed from the front panel.
These operations are generally used in post installation and maintenance modes.
Table 20 Control/Operations
Alarm Cut-Off
Temporarily cuts-off (Turns off) the on-bard audible alarm.
Start Lamp Test
Temporarily illuminates all status indicators of attached rectifiers, distribution
monitoring and control modules and the system controller.
Restart Devices
Provides the ability to restart All system serial controlled rectifiers and/or
converters at once. Provides the ability to individually reset only rectifiers or
converters at a time. This operation does not affect rectifiers, converters, and
other system devices that are already functioning.
Clear Events
Used to clear momentary events or alarms. It clears the following system
alarms: Check Battery, Reserve Time Low, Battery Voltage Imbalance