Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 75
Table 20 Control/Operations
Uninstall Equipment Clears alarms related to the removal of a system component such as a rectifier,
converter, thermal probe, or voltage monitoring module.
Running this
command allows the system controller to retake inventory of using equipment.
Clear History
This area of the menus system can be used to clear the various items that the
controller maintains history records. Once cleared the controller begins to keep
history of new events.
Alarm History Clears only alarm event history.
BD History Clear only BD network access history.
Rectifier History Clears only rectifier event history.
Converter History Clears only converter event history.
Boost History Clears only Boost event history.
Local Port History Clears only local port access event history.
Modem History Clears only Modem port access event history.
Network History Clears only network access history.
All History Single command to clear all history.
Clear Statistics
This area of the menus system can be used to clear the various items that the
controller maintains statistical records. Once cleared the controller begins to
keep new statistical data.
Clear Basic Clears individually or as a group the Basic statistical data kept on
Plant Load, the highest battery temperature, and ambient.
Clear Trend Clears the trend data kept on the plant load.
Clear BD Clears the Battery on Discharge (BD) statistics kept on the plant
load and voltage during discharge.
Alarm Test Provides ability to initiate an alarm test on a specific user selected output relay
or all output relays. Alarm relays are asserted at the configured alarm interval.
Start Battery Test
Initiates the manual battery test feature. A stop battery test operation is
displayed to interrupt the testing and return the unit to normal operation. The
manual battery test utilizes the configured test duration and a system bus
voltage threshold to represent the end of reserve.
Disconnects Provides individual manual control of up to four Low Voltage Disconnects
(LVBD, LVLD1-3) for maintenance purposes.
Enter Boost
Initiates the manual battery Boost feature. A stop battery Boost operation is
displayed to interrupt the Boost operation mode and return the unit to normal
operation.
Load Config Defaults This operation allows a user to bring back all factory defaults with a single
operation. Factory defaults are also custom configuration defaults that are
available. Custom configurations may support multiple factory defaults. Use
caution when applying this command. Previous configuration changes will be
overwritten.
Reset Passwords Resets user, super-user and administrator passwords back to standard defaults.