Table 25 Rectifiers Configuration
and truly act as constant power rectifiers. Settings below 100% will be current
limited to that percentage of the rectifier’s name plate current rating.
Batteries
Table 26 Batteries Configuration
Battery Type
The type of batteries used in the system can be selected from the following
battery types loaded in the Standard controller:
12A100FT
12A150FT
12IR150/150LP 3A125-33L
3A95-21L
3A95-27L
3A95-33L
6A95-13L
6A95-15L
IR30EC
IR40EC L54V63FTX
NCX-125
NCX-80
NSB110FT
NSB170FT
NSB60FT
SE48S63
SE48S80 TEL12-105F
Generic VRLA (Valve Regulated
Lead Acid)
Generic FLOODED (flooded lead
acid)
Generic NiCd (Nickel Cadmium)
Generic Li-ELiTE (Lithium ELiTE)
Generic Li-LMP (Lithium Metal
Polymer)
Once selected the user has the opportunity to automatically accept the
standard defaults for all battery Type related features. Parameters such as float
voltage, float alarms, thermal compensation parameters, etc. are automatically
adjusted if defaults are accepted.
The system factory default is Valve-Reg.
String Capacity
Capacity of an individual battery string in the system which is used to derive the
total installed system battery capacity. This value has to be entered for Generic
battery types but is automatically configured for specific battery models. The
value configured should be the rating to 1.75V at an 8-hr discharge rate.
The available range is 0-
9999 AH. The system factory default is 0 AH
corresponding to the Generic Valve-Reg.
Battery Strings
The total number of battery string installed in the system entered by the user
for inventory purposes and initial reserve time calculations. This value is
automatically configured when using smart lithium batteries. Available range is
0-16. The Infinity NE system factory default is four strings of CSL-12100
batteries.
Cells Per String
The number of basic battery cells that make up a battery string.
The available range is 1-75 cells with a factory default of 24 and 12 cells for -48V
and +24V systems, respectively.