Instruction Manual

Pulsar Plus Controller Family
Issue 7 December 2011 88
System Settings
Table 31 System Settings Configuration
Display Contrast Allows display back-light intensity to be adjusted for contrast in local ambient
light. Factory default is 50%.
Date
Sets system date and format. The format for date can be selected from:
mm/dd/yyyy, dd/mm/yyyy, yyyy/mm/dd, mm-dd-yyyy, yyyy-mm-dd, dd-mm-
yyyy, mm/dd/yy, yy/mm/dd, dd/mm/yy, mm-dd-yy, yy-mm-dd, or dd-mm-yy
and the format for time can be 12HR/24HR format. The factory default is Date:
mm/dd/yyyy and Time: 24HR.
Time Sets system date and fo
rmat. The format for date can be selected from:
mm/dd/yyyy, dd/mm/yyyy, yyyy/mm/dd, mm-dd-yyyy, yyyy-mm-dd, dd-mm-
yyyy, mm/dd/yy, yy/mm/dd, dd/mm/yy, mm-dd-yy, yy-mm-dd, or dd-mm-yy
and the format for time can be 12HR/24HR format. The factory default is Date:
mm/dd/yyyy and Time: 24HR.
Daylight Savings Enable or disable. The factory default is Enabled.
Display T Units °C or °F. The factory default is °C.
Languages Allows the language support to be set between English and Other. Other is a
secondary language such as Spanish or French.
High Ambient T High ambient temperature alarm threshold that can be set from 30°C to 75°C.
This temperature is measured on-board the controller. The factory default
setting is 75°C.
Low Ambient T Low ambient temperature alarm threshold that can be set from -40°C to 10°C.
This temperature is measured on-board the controller. The factory default
setting is -40°C.
Communication Ports
Menus for configuring the following communication parameters:
Table 32 Communication Ports Configuration
Port Type Sets the RS-232
asynchronous serial communication port for either Local
terminal or Modem application.
Factory default is Local.
Local Port Settings
Provides the ability to Enable or Disable Write access to the controller, the
ability to change system settings through the SNMP management or local port.
The factory default setting is enabled.
The baud rate, number of data bits, parity, number of stop bits, and flow
control parameters for the port is also configurable. These parameters have
been factory set to 9600, 8, none, 1, none, respectively.