GE Caliber Series Submittal
Rev. June 2020
CALIBER SERIES SUBMITTAL
Electrical Requirement
Power Supply
208/230V, 1 Phase,
60 HZ
Operating Voltage Range 187~253 VAC
Recommended Fuse/Breaker Size 20A
MCA 17A
Cooling Performance
Rated Cooling Capacity 18,000 BTU
Cooling Capacity Range 5,000~19,000 BTU
Rated Power input 1,650 W
SEER 16.0
EER 10.0
Heating Performance
Rated Heating Capacity 19,000 BTU
Heating Capacity Range 5,400~22,000 BTU
HSPF 9.0
Operating Range
Cooling 0~115°F (-18~46°C)
Heating -4~75°F (-20~24°C)
18,000 BTU 16 SEER WALL MOUNT SINGLE-ZONE HEAT PUMP SYSTEM
ASH118CRDWA / ASYW18CRDWA
CUS
Intertek
Pipe Length
Minimum Pipe Length 6 ft
Maximum Pipe Length 83 ft
Maximum Pipe Height Dierence 50 ft
Connection
1/4”(Discharge)
1/2”(Suction) Flare
Remote Controller
Ships with indoor unit
Wired Controller
Compatible with wired controller ACT17CWA with
interface kit WK-B
WiFi
Compatible with WiFi USB adapter AWF01RWA
Wind Bae
Uses wind bae QAWB37A
Connecting cable to indoor units must be 14/4 AWG unshielded stranded
copper. Cable must be ran continuous, without splicing.
ACCESSORIES
For more information visit us:
www.geappliances.com/ductless
Job Name: _______________________________
Purchaser: _______________________________
Submitted To: ____________________________
Construction: ____________________________
Reference: _______________________________
Approval: ________________________________
Date: ___________________________________
Submitted By: ___________________________
Unit: ___________________________________