Cooling Rated Capacity Btu/hr 9,000 12,000 15,000 17,000 22,000
Capacity Range Btu/hr 3200-12500 3300-15000 5400-24000 5400-26500 6400-30000
Rated Power Input W 620 960 1,200 1,360 1,760
SEER 23.5 23.0 21.5 21.0 20.0
EER 14.5 12.5 12.5 12.5 12.5
Moisture Removal Pt./h 3.50 3.90 4.10 4.30 7.00
Heating Rated Heating Capacity
47°F Btu/hr
10,000 13,000 16,000 22,000 27,600
Heating Capacity Range
Btu/hr
3800-15600 3900-20000 4000-26000 4000-30000 6200-36000
Rated Power Input W 680 1,500 1,700 2,100 2,630
HSPF 10.5 11.0 10.5 10.5 10.0
Rated Heating Capacity
17°F Btu/hr
7,500 10,700 12,000 14,000 19,000
Max. Heating Capacity 17°F
Btu/hr
13,000 15,000 17,000 19,000 26,000
Max. Heating Capacity 5°F
Btu/hr
10,000 13,000 16,000 17,000 20,000
Max Heating Capacity
-4F°F Btu/hr
8,500 10,000 12,000 14,000 15,000
Max Heating Capacity-15°F
Btu/hr
6,500 7,500 10,000 12,000 14,000
100% heating capacity
@5F
Yes Yes Yes No No
Operating
Range
Cooling °F(°C) 14~115(-10~46) 14~115(-10~46) 14~115(-10~46) 14~115(-10~46) 14~115(-10~46)
Heating °F(°C) -15~75(-26~24) -15~75(-26~24) -15~75(-26~24) -15~75(-26~24) -15~75(-26~24)
Power Supply Voltage, Cycle, Phase V/
Hz/-
208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1
Outdoor Unit Compressor Type DC inverter Driven Rotary
Maximum Fuse Size A 15 15 20 20 30
Minimum Circuit Amp A 11.0 11.0 14.0 14.0 20.0
Outdoor Noise Level dB 54 54 55 55 57
Dimension: Height in (mm) 23 1/2 (597) 23 1/2 (597) 27 7/16 (697) 27 7/16 (697) 30 (762)
Dimension: Width in (mm) 30 11/16 (780) 30 11/16 (780) 35 (890) 35 (890) 36 3/16 (920)
Dimension: Depth in (mm) 11 7/16 (290) 11 7/16 (290) 13 7/8 (353) 13 7/8 (353) 15 1/8 (385)
ODU Weight (Ship/
Net)- lbs
90.2/78.3 90.2/78.3 117.5/100.3 117.5/100.3 149.5/130.1
Indoor Unit Fan Speed Stages 5 + Auto 5 + Auto 5 + Auto 5 + Auto 5 + Auto
Indoor Sound Level dB
(Turbo/High/Med/Low/
Quiet)
44/40/35/31/23 45/41/36/32/23 48/46/42/36/34 48/46/42/36/34 49/47/42/36/34
Dimension: Height in (mm) 12 1/4 (310) 12 1/4 (310) 13 1/4 (336) 13 1/4 (336) 13 1/4 (336)
Dimension: Width in (mm) 35 7/16 (900) 35 7/16 (900) 43 7/8 (1115) 43 7/8 (1115) 43 7/8 (1115)
Dimension: Depth in (mm) 8 7/16 (215) 8 7/16 (215) 9 9/16 (243) 9 9/16 (243) 9 9/16 (243)
IDU Weight (Ship/Net)- lbs 30.9/25.4 30.9/25.4 43.2/35.3 43.2/35.3 45.4/37.5
Refrigerate Line Connections Flare Flare Flare Flare Flare
Liquid O.D. in 1/4 1/4 1/4 1/4 1/4
Suction O.D. in 3/8 3/8 1/2 1/2 1/2
Factory Charge Oz 38.8 38.8 52.2 52.2 74.1
Maximum Line Length
Ft / m
50/15 50/15 83/25 83/25 83/25
Maximum Height Ft / m 33/10 33/10 50/15 50/15 50/15
FEATURES &
BENEFITS
TURBO MODE
Cools or heats
the room quickly
QUIET MODE
Minimizes indoor
noise while
maintaining
comfort levels
-15˚F
-15˚F HEATING
Low ambient
heating down to
-15F (-26C)
3D AIR FLOW
Delivers air vertically
and horizontally for
even distribution
throughout the room
LONG DISTANCE
AIR SUPPLY
Optimized fan
motor and
blower design
enables up to 60
feet of air flow
BLUE FIN
A special coating
that whisks away
condensate water
WARM START
Ensures the fan
will not blow cold
air during heating
mode startup
Automatically
adjusts airflow
upward when
cooling, or
downward
when heating
AUTO LOUVER
Leading compressor
technology for
maximum comfort
and eciency
A-PAM DC INVERTER
BASE PAN HEATER
Prevents condensed
water from freezing
and blocking the
base pan
drain openings
Remotely control
ductless system
from any smart
phone or tablet
OPTIONAL WIFI
CONTROL
Operating Range (
O
F):
1151450-4
-15
Cooling
Heating
75