GE Altitude Series Submittal

ALTITUDE SERIES SUBMITTAL
Rev. May 2020
Electrical Requirement
Power Supply
208/230V, 1 Phase,
60 HZ
Operating Voltage Range 187~253 VAC
Recommended Fuse/Breaker Size 20A
MCA 14A
Operating Range
Cooling 14~115°F (-10~46°C)
Heating -15~75°F (-26~24°C)
CUS
Intertek
15000 BTU/HR WALL MOUNTED INVERTER DRIVEN HEAT PUMP SYSTEM
ASH115PRDWA / ASYW15PRDWB
Pipe Length
Minimum Pipe Length 6 ft
Maximum Pipe Length 83 ft
Maximum Pipe Height Dierence 50 ft
Connection
1/4”(Discharge)
1/2”(Suction) Flare
Heating Performance
Rated Heating Capacity 16,000 BTU
Heating Capacity Range 4,000~26,000 BTU
Rated Power Input 1,700 W
HSPF 10.5
Cooling Performance
Rated Cooling Capacity 15,000 BTU
Cooling Capacity Range 5,400~24,000 BTU
Rated Power input 1,200 W
SEER 21.5
EER 12.5
Moisture Removal 4.1 Pt./Hr
ACCESSORIES
Remote Controller
Ships with indoor unit
Wired Controller
ASYW15PRDWB units are compatible with wired
controller ACT17CWA with the interface kit WK-B
WiFi
ASYW15PRDWB units are compatible with WiFi USB
adapter AWF01RWA