SUBMITTALS MultiLink Series Rev. Aug. 2022 Outdoor ASH218JCDDA ASH324JCDDA ASH436JCDDA For more information visit us: www.geappliances.
Revision History Rev. June 2022 - Submittal edition release. Rev. Aug. 2022 - USYM18, USYF18 18K ID vapor line correction. Controller updates.
Matching Tables No adapter is shipped with ASH2 ASH218JCDDA ASH436JCDDA Combinations Port A 1/4" x 3/8" 1/4" x 3/8" 7 9 9 12 12 12 7 7 9 7 9 12 Two Zone Combinations Required Adapter Port B Port D Two Zone ASH324JC ships with adapter D Combinations Port C Port B Port A MS: 1/4" x 3/8" EH: 1/4" x 1/2" 1/4" x 3/8" 1/4" x 3/8" 7 9 9 12 12 12 18 18 18 7 9 9 12 9 12 12 12 18 12 7 7 9 7 9 12 7 9 12 7 7 9 7 9 9 9 12 7 12 ------------------7 7 7 7 9 7 9 7 7 9 Two Zone Three Zone Required A
MULTILINK SERIES SUBMITTAL 18000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM ASH218JCDDA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:_________
MULTILINK SERIES SUBMITTAL 18000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM ASH218JCDDA 14 1/2 (368) 16 1/8 (410) Air inlet 3/4 (20) 2U18MS2HDA Air inlet Air outlet 2 3/4 (70) 1 (26) A unit connection B unit connection 13 7/8 (353) 3/4 (19) 27 1/2 (700) Handle Liquid Connection Ø All Ports - 1/4 Flare 13 3/8 (340) 5 1/8 (130) 25 (635) 36 (915) Vapor Connection Ø All Ports - 3/8 flare 14 1/2 (368) 16 1/8 (410) Air inlet 3/4 (20) 3U24MS2HDA Air inlet Air outlet 13 7/8 (353) 3/4
MULTILINK SERIES SUBMITTAL 18000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM ASH218JCDDA Heating Capacity Data - Non Ducted Indoor Set Temperature Outdoor Air Temp DB Maximum Heating Capacity (Btu/h) -4OF (-20OC) 5OF (-15OC) 17OF (-8OC) 47OF (8OC) 11,970 14,385 15,960 25,200 60 F (16 C) O 70OF (21OC) O Power Usage (w) COP 1,935 2,255 1,725 2,535 Max Heating Capacity (Btu/h) 1.81 1.87 2.71 2.91 11,400 13,700 15,200 24,000 77OF (25OC) Power Usage (w) COP 1,910 2,230 1,700 2,510 1.75 1.
MULTILINK SERIES SUBMITTAL 24000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM ASH324JCDDA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:_________
13 7/8 3/4 (19) MULTILINK SERIES SUBMITTAL 5 1/8 (130) 25 (635) 36 (915) 24000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM Vapor Connection Ø All Ports - 3/8 flare ASH324JCDDA 3/4 (20) 3U24MS2HDA 14 1/2 (368) 16 1/8 (410) Air inlet Air inlet Air outlet 2 3/4 (70) 1 (26) A unit connection B unit connection C unit connection 13 7/8 (353) 3/4 (19) 27 1/2 (700) Handle Liquid Connection Ø All Ports - 1/4 Flare 13 5/8 (340) 5 1/8 (130) 25 (635) 36 (915) Vapor Connection Ø All Ports - 3/8
MULTILINK SERIES SUBMITTAL 24000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM ASH324JCDDA Heating Capacity Data - Non Ducted Indoor Set Temperature Outdoor Air Temp DB Maximum Heating Capacity (Btu/h) -4OF (-20OC) 5OF (-15OC) 17OF (-8OC) 47OF (8OC) 12,600 14,595 21,000 31,500 60 F (16 C) O 70OF (21OC) O Power Usage (w) COP 2,095 2,065 2,595 2,845 Max Heating Capacity (Btu/h) 1.76 2.07 2.37 3.25 12,000 13,900 20,000 30,000 77OF (25OC) Power Usage (w) COP 2,070 2,040 2,570 2,820 1.70 2.
MULTILINK SERIES SUBMITTAL 36000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM ASH436JCDDA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:_________
2 13 7/8 (3 3/4 (19) B unit connection C unit connection MULTILINK SERIES SUBMITTAL 5 1/8 (130) 25 (635) Vapor Connection 36000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM 36 (915) Ø All Ports - 3/8 flare ASH436JCDDA Air outlet 16 1/8 (410) Air inlet 18 1/8 (460) 14 5/8 (370) Air inlet 1 3/4 (45) 3/4 (20) 4U36MS2HDA Liquid pipe Ø All Ports - 1/4 flare 2 5/8 (68) Handle 15 3/8 (390) Handle 37 7/8 (962) Handle A unit connection B unit connection 7/8 (23) C unit connection D unit co
MULTILINK SERIES SUBMITTAL 36000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM ASH436JCDDA Heating Capacity Data - Non Ducted Indoor Set Temperature Outdoor Air Temp DB Maximum Heating Capacity (Btu/h) -4OF (-20OC) 5OF (-15OC) 17OF (-8OC) 47OF (8OC) 18,900 23,100 31,500 45,360 60 F (16 C) O 70OF (21OC) O Power Usage (w) COP 3,125 3,705 4,725 4,825 Max Heating Capacity (Btu/h) 1.77 1.83 1.95 2.76 18,000 22,000 30,000 43,200 77OF (25OC) Power Usage (w) COP 3,100 3,680 4,700 4,800 1.70 1.
MULTILINK SERIES SUBMITTAL 7,000 BTU/HR WALL MOUNTED INVERTER DRIVEN HEAT PUMP SYSTEM ASYW07CRDDA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:_______
MULTILINK SERIES SUBMITTAL 9,000 BTU/HR WALL MOUNTED INVERTER DRIVEN HEAT PUMP SYSTEM ASYW09CRDDA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:_______
MULTILINK SERIES SUBMITTAL 12,000 BTU/HR WALL MOUNTED INVERTER DRIVEN HEAT PUMP SYSTEM ASYW12CRDDA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:______
MULTILINK SERIES SUBMITTAL 18,000 BTU/HR WALL MOUNTED INVERTER DRIVEN HEAT PUMP SYSTEM ASYW18CRDDA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:______
MULTILINK SERIES SUBMITTAL 24,000 BTU/HR WALL MOUNTED INVERTER DRIVEN HEAT PUMP SYSTEM ASYW24CRDDA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:______
MULTILINK SERIES SUBMITTAL 9000 BTU/HR CASSETTE TYPE INDOOR AB09SC2VHA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:________________________________
MULTILINK SERIES SUBMITTAL 9000 BTU/HR CASSETTE TYPE INDOOR AB09SC2VHA ⑥ ⑥ Part Name 1 Vapor Pipe 2 Liquid Pipe 3 Drain Pump Outlet 4 Fresh Air Inlet 5 Air Return Grille 6 Air Supply More than 59 (1500) to wall on all sides 4 3/4 (120) ③ ② ① 1 inch recess between ceiling surface and bottom of unit without panel on.
MULTILINK SERIES SUBMITTAL 12000 BTU/HR CASSETTE TYPE INDOOR AB12SC2VHA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:________________________________
MULTILINK SERIES SUBMITTAL 12000 BTU/HR CASSETTE TYPE INDOOR AB12SC2VHA ⑥ ⑥ Part Name 1 Vapor Pipe 2 Liquid Pipe 3 Drain Pump Outlet 4 Fresh Air Inlet 5 Air Return Grille 6 Air Supply More than 59 (1500) to wall on all sides 4 3/4 (120) ③ ② ① 1 inch recess between ceiling surface and bottom of unit without panel on.
MULTILINK SERIES SUBMITTAL 18000 BTU/HR CASSETTE TYPE INDOOR AB18SC2VHA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:________________________________
MULTILINK SERIES SUBMITTAL 18000 BTU/HR CASSETTE TYPE INDOOR AB18SC2VHA ⑥ ⑥ Part Name 1 Vapor Pipe 2 Liquid Pipe 3 Drain Pump Outlet 4 Fresh Air Inlet 5 Air Return Grille 6 Air Supply More than 59 (1500) to wall on all sides 4 3/4 (120) ③ ② ① 1 inch recess between ceiling surface and bottom of unit without panel on.
MULTILINK SERIES SUBMITTAL 9000 BTU/HR MID-STATIC DUCTED INDOOR USYM09UCDSA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:_____________________________
MULTILINK SERIES SUBMITTAL 9000 BTU/HR MID-STATIC DUCTED INDOOR USYM09UCDSA 12 1/2 (317) 7 5/8 (195) ⑤ 15 3/4 (400) ⑥ 1 (25) 1 1/8 (30) 6 1/2 (166) ① Air flow 9 3/8 (238) ④ ③ ② 1 3/8 (35) 1 3/4 (44) ⑦ 9 3/4 (248) 5 (128) 6 1/4 (158) 3 7/8 (100) Reversable fresh air supply adapter 27 1/2 (700) 24 3/8 (620.
MULTILINK SERIES SUBMITTAL 12000 BTU/HR MID-STATIC DUCTED INDOOR USYM12UCDSA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:____________________________
MULTILINK SERIES SUBMITTAL 12000 BTU/HR MID-STATIC DUCTED INDOOR USYM12UCDSA 12 1/2 (317) 7 5/8 (195) ⑤ 15 3/4 (400) ⑥ 1 (25) 1 1/8 (30) 6 1/2 (166) ① Air flow 9 3/8 (238) ④ ③ ② 1 3/8 (35) 1 3/4 (44) ⑦ 9 3/4 (248) 5 (128) 6 1/4 (158) 3 7/8 (100) Reversable fresh air supply adapter 27 1/2 (700) 24 3/8 (620.
MULTILINK SERIES SUBMITTAL 18000 BTU/HR MID-STATIC DUCTED INDOOR USYM18UCDSA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:____________________________
MULTILINK SERIES SUBMITTAL 18000 BTU/HR MID-STATIC DUCTED INDOOR ① ⑤ 15 3/4 (400) ⑥ 1 (25) Air flow 1 1/8 (30) 6 1/2 (166) ④ ③ ② 1 3/8 (35) 1 3/4 (44) 9 3/8 (238) 12 1/2 (317) 7 5/8 (195) 3 7/8 (100) ⑦ 9 3/4 (248) 6 1/4 (158) 5 (128) USYM18UCDSA Reversable fresh air supply adapter 27 1/2 (700) 24 3/8 (620.
MULTILINK SERIES SUBMITTAL 24000 BTU/HR MID-STATIC DUCTED INDOOR USYM24UCDSA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:____________________________
MULTILINK SERIES SUBMITTAL 24000 BTU/HR MID-STATIC DUCTED INDOOR ① ⑤ 15 3/4 (400) ⑥ 1 (25) Air flow 1 1/8 (30) 6 1/2 (166) ④ ③ ② 1 3/8 (35) 1 3/4 (44) 9 3/8 (238) 12 1/2 (317) 7 5/8 (195) 3 7/8 (100) ⑦ 9 3/4 (248) 6 1/4 (158) 5 (128) USYM24UCDSA Reversable fresh air supply adapter 27 1/2 (700) 24 3/8 (620.
MULTILINK SERIES SUBMITTAL 9000 BTU/HR FLOOR CONSOLE INDOOR USYF09UCDWA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:________________________________
MULTILINK SERIES SUBMITTAL 9000 BTU/HR FLOOR CONSOLE INDOOR USYF09UCDWA 24 3/4 (630) 2 1/2 (65) 5/8 (16) 3/4 (20) 4 1/2 (115) 8 5/8 (220) 3/4 (20) 27 1/2 (700) 23 5/8 (600) 3 1/8 (80) 3 1/2 (90) 8 3/4 (223) ⑤ ② 7 1/8 (181) 3 1/2 (90) 3 1/8 (80) ③ ④ ② 26 1/8 (663) 25 1/8 (639) 16 (406) 3 1/4 (84) 3 1/4 (84) ⑦ ⑦ 5 7/8 (150) 21 1/8 (535) 22 7/8 (581) 19 3/8 (492) 9 (228) 5 3/4 (145) ⑥ # 1 2 3 4 5 6 7 Description Screw holes for floor install Side knockout Liquid pipe connection Vapor
MULTILINK SERIES SUBMITTAL 12000 BTU/HR FLOOR CONSOLE INDOOR USYF12UCDWA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:________________________________
MULTILINK SERIES SUBMITTAL 12000 BTU/HR FLOOR CONSOLE INDOOR USYF12UCDWA 24 3/4 (630) 2 1/2 (65) 5/8 (16) 3/4 (20) 4 1/2 (115) 8 5/8 (220) 3/4 (20) 27 1/2 (700) 23 5/8 (600) 3 1/8 (80) 3 1/2 (90) 8 3/4 (223) ⑤ ② 7 1/8 (181) 3 1/2 (90) 3 1/8 (80) ③ ④ ② 26 1/8 (663) 25 1/8 (639) 16 (406) 3 1/4 (84) 3 1/4 (84) ⑦ ⑦ 5 7/8 (150) 21 1/8 (535) 22 7/8 (581) 19 3/8 (492) 9 (228) 5 3/4 (145) ⑥ # 1 2 3 4 5 6 7 Description Screw holes for floor install Side knockout Liquid pipe connection Vapor
MULTILINK SERIES SUBMITTAL 15000 BTU/HR FLOOR CONSOLE INDOOR USYF18UCDWA Job Name:________________________________ Approval:_________________________________ Purchaser:________________________________ Date: ____________________________________ Submitted To: ____________________________ Submitted By: ____________________________ Construction: _____________________________ Unit: ____________________________________ Reference:________________________________ Drawing #:________________________________
MULTILINK SERIES SUBMITTAL 15000 BTU/HR FLOOR CONSOLE INDOOR USYF18UCDWA 24 3/4 (630) 2 1/2 (65) 5/8 (16) 3/4 (20) 4 1/2 (115) 8 5/8 (220) 3/4 (20) 27 1/2 (700) 23 5/8 (600) 3 1/8 (80) 3 1/2 (90) 8 3/4 (223) ⑤ ② 7 1/8 (181) 3 1/2 (90) 3 1/8 (80) ③ ④ ② 26 1/8 (663) 25 1/8 (639) 16 (406) 3 1/4 (84) 3 1/4 (84) ⑦ ⑦ 5 7/8 (150) 21 1/8 (535) 22 7/8 (581) 19 3/8 (492) 9 (228) 5 3/4 (145) ⑥ # 1 2 3 4 5 6 7 Description Screw holes for floor install Side knockout Liquid pipe connection Vapor