GE Endure Multi Series Submittal

ENDURE MULTI SERIES SUBMITTAL
Rev. June 2020
Cooling Performance
Cooling Capacity Range
(Non-Ducted/Ducted)
5,000~34,000 BTU/
5,000~34,400 BTU
Rated Power Input
(Non-Ducted/Ducted)
2,720/3,440 W
SEER (Non-Ducted/Ducted) 20.0/17
EER (Non-Ducted/Ducted) 12.5/10.0
Heating Performance
Heating Capacity Range
(Non-Ducted/Ducted)
6,100~36,000 BTU/
6,100~35,000 BTU
HSPF (Non-Ducted/Ducted) 10.5/10.5
36000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM
ASH436NCDWA
Outdoor Unit
Compressor DC inverter Driven Rotary
Uncrated Dimension (HxWxD)
33 1/8 x 37 3/8 x 13 3/8 in
(840 x 948 x 340 mm)
Crated (HxWxD)
37 3/8 x 37 1/2 x 15 3/8 in
(956 x 951 x 390 mm)
Outdoor Sound Rating dB 59
Heat Exchanger Fin Type Blue Fin
Weight (Ship/Net) 215/198.4 lbs
Factory Refrigerant Charge R-410A (113 oz)
Electrical Requirement
Power Supply
208/230V, 1 Phase,
60 HZ
Operating Voltage Range 187~253 VAC
Recommended Fuse/Breaker Size 40A
MCA 30A
Operating Range
Cooling 23~115°F (-5~46°C)
Heating -15~77°F (-26~25°C)
Pipe Length
Minimum Pipe Length (Each) 6 ft
Maximum Pipe Length (Each/All) 82 ft /230 ft
Maximum Pipe Height Dierence 50 ft
Flare Connections
Liquid:
1/4”, 1/4”, 1/4”, 1/4”
Vapor:
3/8”, 3/8”, 3/8”, 1/2”
Rated heating performance down to -15°F and continuous operation at -22°F
Connecting cable to indoor units must be 14/4 AWG unshielded stranded
copper. Cable must be ran continuous, without splicing.
Accessories
Wind Bae
Uses wind bae UAWB46A
Snow Hood
Uses snow hood UAWB80A
Job Name: ____________________________
Purchaser: ____________________________
Submitted To: _________________________
Construction: _________________________
Reference: ____________________________
Approval: _____________________________
Date: ________________________________
Submitted By: ________________________
Unit: ________________________________
Drawing #: ____________________________