GE QACT17A User Manual

16
A B C
Indoor 2
Wired controller
A B C
A B C
A B C
Indoor 1
Wired controller
A B C
A B C
Indoor N
Wired controller
Indoor 15
Wired controller
Indoor 16
(master unit)
Wired controller
Control wiring of wired
controller, polar.
Wired controller
B: One Controller for up to 16 indoor
1. Cassette (AB…AL…MVAB…MVAL…)
Ducted (AD…AM24…MVAD…MVAH…)
MRV Wall Mount (MVAW…)
A B C
Indoor 2
Wired controller
A B C
A B C
A B C
Indoor 1
Wired controller
A B C A B C
Indoor N
Wired controller
Indoor 15
Wired controller
Indoor 16
(master unit)
Wired controller
Control wiring of wired
controller, polar.
Wired controller
2. Ducted (AM36...AM48…)
Addressing Indoor Units
Each indoor unit must hvae a unique
address.
Compact Cassette (AB…) use SW02_1-4
Large Cassette (AL…) use SW3_5-8
Slim Duct (AD…) use SW03_1-4
High Static Duct (AM24…) use SW03_5-8
High Static Duct (AM36…AM48…) use
SW02_1-4
All MRV indoor (MV…) use SW01_1-4
Dipswitch position Dipswitch position
Unit # 1 2 3 4 Unit # 1 2 3 4
5 6 7 8 5 6 7 8
0* o o o o 8 on o o o
1 o o o on 9 on o o on
2 o o on o 10 on o on o
3 o o on on 11 on o on on
4 o on o o 12 on on o o
5 o on o on 13 on on o on
6 o on on o 14 on on on o
7 o on on on 15 on on on on
* Unit 0 is connected directly to the control and is master