Installation Instructions
31-10986-2
4
Installation Instructions
1
The following MINIMUM clearance 
dimensions must be maintained.
PREPARING THE OPENING
2
APPROXIMATE COOKTOP 
DIMENSIONS
5
Make sure the wall coverings, countertop and 
cabinets around the cooktop can withstand 
heat (up to 200°F) generated by the cooktop.
4
CUTOUT DIMENSIONS OF THE 
COUNTERTOP
To insure accuracy, it is best to make a template 
when cutting the opening in the counter.
13" MAX. 
Depth of 
uprotected 
overhead 
cabinets
30" MIN. 
Clearance from 
countertop to 
unprotected 
overhead 
surface
2" MIN. Clearance 
from cutout to side wall 
on the left of the unit
15" MIN. Height 
from countertop 
to nearest cabinet 
on either side of 
unit
2" MIN. Clearance 
from cutout to 
side wall on the 
right of the unit
21"
28-1/4"
Cooktop
29-3/4" 
(29-7/8" SS)
19-3/8"
4-5/8“ at baffle 
near center of 
unit 
3-1/4” at rear
2-1/2" Min. from front 
edge of cutout and front 
edge of countertop
19-5/8" to 19-3/4” 
depth of cutout
28-1/2" 
to 28-5/8” 
width of 
cutout
1-3/4" Min. Between 
cutout and the wall 
behind the cooktop
Wall coverings, 
cabinets and 
countertop must 
withstand heat 
up to 200°F. 
If a 30" clearance between the cooking surface 
and overhead combustible materials or metal 
cabinets cannot be maintained, a minimum 
clearance of 24" is required and the underside 
of the cabinets above the cooktop must be 
protected with not less than 1/4" insulating 
millboard covered with sheet metal not less than 
0.0122" thick.
Use a 30” or wider cabinet 
base.
3
VERTICAL CLEARANCES
Allow 3” minimum vertical clearance for air space from 
the cooktop bottom 
(or 5-7/8” minimum depth from 
the countertop) to any combustible surfaces, such 
as a cabinet drawer.
6
FOR AMERICANS WITH DISABILITIES 
ACT (ADA) FORWARD APPROACH 
INSTALLATION ONLY:
Allow 5” minimum 
depth between the 
countertop and an 
enclosure.
NOTE: The enclosure must be made 
of at least 1/4” wood material. Also, 
an access panel is required for the 
junction box, hold-down brackets, 
and service.
DRAWER
3" 
5-7/8" 
5”
See label next 
to name plate 
for minimum 
clearance to 
rear wall.
3
VERTICAL CLEARANCES (Cont.)
The cooktop needs 7 cubic feet of cooling air 
below the counter (5 horizontal feet of cabinet for 
ventilation). The wood divider only needs to be 
located directly below the unit.
1” = 2.5 cm; 1’ = 0.3 m