User guide

ZTS Series
Withstand Ratings
PB-5066
P
age 8
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
150,000
N/A
150,000
150,000
150,000
150,000
150,000
150,000
200,000
200,000
200,000
200,000
200,000
150,000
150,000
150,000
150,000
150,000
150,000
150,000
150,000
200,000
200,000
200,000
200,000
ZTSCT10 (2)
ZTSCT15 (2)
ZTSCT22 (2)
ZTSCT26 (2)
ZTSCT40 (2)
ZTSCT60 600 750 800 65,000 50,000 50,000 42,000
ZTSCT80 800 1000 1200 65,000 N/A 50,000 N/A
ZTSCT100 1000 1250 1600 85,000 65,000 50,000 42,000
ZTSCT120 1200 1500 1600 85,000 65,000 50,000 42,000
ZTSCT160 1600 2000 2500 100,000 85,000 100,000 85,000
ZTSCT200 2000 2500 2500 100,000 85,000 100,000 85,000
ZTSCT300 3000 4000 4000 100,000 85,000 100,000 85,000
ZTSCT400 4000 6000 5000 100,000 85,000 100,000 85,000
ZBTSD10 (2) 100 125 800 50,000 42,000 35,000 35,000
ZBTSD15 (2) 150 200 800 50,000 42,000 35,000 35,000
ZBTSD22 (2) 225 300 800 50,000 42,000 35,000 35,000
ZBTSD26 (2) 260 350 800 50,000 42,000 35,000 35,000
ZBTSD40 (2) 400 600 800 50,000 42,000 35,000 35,000
ZBTSD60 600 750 800 65,000 50,000 50,000 42,000
ZBTSD80 800 1000 1600 85,000 65,000 50,000 42,000
ZBTSD100 1000 1250 1600 85,000 65,000 50,000 42,000
ZBTSD120 1200 1500 1600 85,000 65,000 50,000 42,000
ZBTSD160 1600 2000 2500 100,000 85,000 100,000 85,000
ZBTSD200 2000 2500 2500 100,000
85,000
100,000 85,000
ZBTSD300 3000 4000 4000 100,000 85,000 100,000 85,000
ZBTSD400 4000 6000 5000 100,000 85,000 100,000 85,000
ZTSD160 (2)
1600
2000 2500
100,000
85,000
100,000
85,000
ZTSD200 (2) 2000 2500 2500 100,000 85,000 100,000 85,000
ZTSD300 (2) 3000 4000 4000 100,000 85,000 100,000 85,000
ZTSD400 (2) 4000 6000 5000 100,000 85,000 100,000 85,000
GE Zenith
Model No.
UL 1008
ZTS Switch
Rating
GE Zenith ZTS Switches
Rated for Total Systems or Motor Loads (1)
Withstand and Closing Current Ratings per UL
1008 and
CSA
Maximum
Fuse Size
Amps
Maximum
Circuit Amps
at 480 VAC
(
UL)
Maximum
Circuit Amps
at 600 VAC
(
CSA)
Maximum
Circuit
Breaker
Size Amps
Maximum
Circuit Amps
at 480 VAC
(
UL)
Maximum
Circuit Amps
at 600 VAC
(
CSA)
Maximum
Circuit Amps
at 480 VAC (
UL)
Maximum
Circuit Amps
at 600 VAC (
CSA
)
Current Limiting Fuse
Specific Coordinated
Breaker Rating (3)
Any Molded Case
Breaker Rating
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
150,000
150,000
150,000
150,000
150,000
150,000
150,000
150,000
ZBTSCT10 (2) 100
ZBTSCT15 (2) 150
ZBTSCT22 (2) 225
ZBTSCT26 (2) 260
ZBTSCT40 (2) 400
ZBTSCT60 600 750 800 65,000 50,000 50,000 42,000
ZBTSCT80 800 1000 1600 85,000 65,000 50,000 42,000
ZBTSCT100 1000 1250 1600 85,000 65,000 50,000 42,000
ZBTSCT120 1200 1500 1600 85,000 65,000 50,000 42,000
ZBTSCT160 1600 2000 2500 100,000 85,000 100,000 85,000
ZBTSCT200 2000 2500 2500 100,000
85,000
100,000 85,000
ZBTSCT300 3000 4000 4000 100,000 85,000 100,000 85,000
ZBTSCT400 4000 6000 5000 100,000 85,000 100,000 85,000
100
150
220
260
400
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000