Quick Specs

AZ65H15DAB
GE Zoneline
®
Heat Pump Unit, 230/208 Volt
DIMENSIONS AND INSTALLATION INFORMATION (IN INCHES)
For answers to your Monogram, GE Café
Series, GE Profile
Series or
GE Appliances product questions, visit our website at geappliances.com
or call GE Answer Center
®
Service, 800.626.2000.
Specification Revised 4/16
ELECTRICAL WIRING
All wiring, including installation of receptacle, must
be made in accordance with local electrical codes
and regulations.
NOTE: Aluminum wiring may pose special problems –
consult a qualified electrician.
GRILLE OPTIONS
Stamped Aluminum Grille – RAG60
Exterior Architectural Louvers Durable Polycarbonate:
RAG61 (Beige) RAG63 (Bittersweet)
RAG62 (Maple) RAG67 (Extruded Aluminum)
RETROFIT KITS:
RAK40 – Deflector Kit to adapt chassis for use with
existing exterior architectural louvered grilles.
DUCTED APPLICATIONS
4500 and 6500 series can be used with ductwork to heat or cool
more than one room. RAK6053 Duct Adaptor is applied to top of
case over air discharge/RAK601B Duct Extension is applied to
right or left of adaptor. Locally fabricated ductwork may be added
to extend to maximum recommended distance of 15 feet.
ELECTRICAL CONNECTION
230/208 volt units may be plugged into a receptacle. 265 volt units
are provided with a junction box and require direct connection. (NEC
Requires 265V Direct Connection) See Architects and Engineers
Design Data Manual for electrical connection information including use
of sub-base for direct connected units. Installation must comply with
local electrical codes and regulations.
POWER CONNECTION KITS REQUIRED ON ALL
ZONELINE CHASSIS.
230/208 VOLT LINE CORD CONNECTED UNITS
LINE
CORD KIT
ELECTRIC
HEAT
(BTUH)
ELECTRIC
HEATER
WATTS
ELECTRIC
HEAT
AMPS
MIN. CIRCUIT
PROTECTION
(AMPS)
RAK315P 8,100/6,600 2,430/2,020 10.6/9.7 15
RAK320P 11,500/9,400 3,450/2,860 15.1/13.8 20
RAK330P 16,300/13,400 4,860/4,020 21.2/19.3 30
230/208 VOLT SUB-BASE CONNECTED UNITS
SUB-BASE
ELECTRIC
HEAT
(BTUH)
ELECTRIC
HEATER
WATTS
ELECTRIC
HEAT
AMPS
MIN. CIRCUIT
PROTECTION
(AMPS)
R A K204D15PA
8,100/6,600 2,430/2,020 10.6/9.7 15
RAK204D20PA
11,500/9,400 3,450/2,860 15.1/13.8 20
R A K204D30PA
16,300/13,400 4,860/4,020 21.2/19.3 30
MAXIMUM CORD EXTENSION
SIDE
VIEW
Inside
Room
Cabinet
Outside
58
21
Grille
7-1/8
RAB71A = 16
RAB77A = 16-1/4
RAB71A = 20-7/8
RAB77A = 21
Room Air/Installation QSart
A
C
B
Zoneline RAC Wall Installation
WALL CASE DIMENSIONS
RAB71B WALL SLEEVE
Heavy-gauge galvanized steel, with
insulation.
A – 42", B – 13-3/4", C – 16"
RAB77B WALL SLEEVE
Molded SMC fiberglass-reinforced
polyester compound.
A – 42-1/8", B– 13-7/8", C – 16-1/4"
WALL OPENING DIMENSIONS
Add 1/4" to A and C dimensions
for all cut-out size.
RAB71B 16-1/4" Min. H x 42-1/4" Min. W
Available in 16", 24", 28" and 31" depths
RAB77B 16-1/2" Min. H x 42-3/8" Min. W