Specification

Automatic Standby Generator Systems
Not for Prime Power or use where standby systems are legally required, for serious life safety or health
hazards, or where lack of power hampers rescue of fire-fighting operation.
1
This generator is rated in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator
assemblies) and CSA (Canadian Standards Association) standard C22.2 No. 100-04 (motors and generators).
35kW
¹
Commercial
Generator Model Options
LP Vapor Natural Gas
Model
Power
(KW)
Alternator L-N L-L Config # Leads Phase
Power
Factor
Hz kW Amps kW Amps Breaker Controller
076040 35 35-BSPP-0 120 240 - 4 1 1.0 60 35 146 31.5 131 175
Briggs & Stratton
Standard
076041 35 35-TBSPP-0 120 208 WYE 12 3 0.8 60 35 121 31.5 109 150 InteliNano
076042 35 35-TBSPP-0 139 240 WYE 12 3 0.8 60 35 105 31.5 95 125 InteliNano
076043 35 35-TBSPP-0 120 240 Delta 12 3 0.8 60 35 105 31.5 95 125 InteliNano
076044 35 35-TBSPP-0 240 416 WYE 12 3 0.8 60 35 61 31.5 55 70 InteliNano
076045 35 35-TBSPP-0 227 480 WYE 12 3 0.8 60 35 53 31.5 47 60 InteliNano
076240 35 35-BSPP-0 120 240 - 4 1 1.0 60 35 146 31.5 131 175 InteliLite
076241 35 35-TBSPP-0 120 208 WYE 12 3 0.8 60 35 121 31.5 109 150 InteliLite
076242 35 35-TBSPP-0 139 240 WYE 12 3 0.8 60 35 105 31.5 95 125 InteliLite
076243 35 35-TBSPP-0 120 240 Delta 12 3 0.8 60 35 105 31.5 95 125 InteliLite
076244 35 35-TBSPP-0 240 416 WYE 12 3 0.8 60 35 61 31.5 53 70 InteliLite
076245 35 35-TBSPP-0 227 480 WYE 12 3 0.8 60 35 53 31.5 47 60 InteliLite