Use and Care Manual

14 BRIGGSandSTRATTON.COM
Setting Exercise Timer
The generator is equipped with an exercise timer. During the
exercise period, the unit runs for approximately 20 minutes
and then shuts down. Electrical load transfer DOES NOT occur
during the exercise cycle (unless an utility power outage
occurs).
The generator will only enter the exercise cycle if the unit is
in the AUTO mode and this exact procedure is followed.
To set the exercise timer:
NOTICE The generator is set with a default exercise cycle
setting of Tuesday at 2:00 P.M, Central Time. To change the
cycle setting, proceed to the following steps:
1. Choose the day and time you want your generator to
exercise.
2. Press and hold the left arrow and right arrow
simultaneously for 3 seconds to enter the General
Set-Up program mode. See General Set-Up flow chart
in Menu Section.
3. Verify and/or set the time and date on the unit.
4. Go to the SET EXERCISE prompt and hit the “OK”
button.
NOTICE Items will flash until they are selected.
SELECT DAY: Use the left or right arrow to toggle
through the days of the week, Once the day is
selected, hit the “OK” button.
SELECT HOUR: Use the left or right arrow to toggle
through between 1 and 12. Choose the hour of day
you want the generator to exercise then hit the “OK”
button.
SELECT MINUTE: Use the left of right arrow to toggle
between :00 and :59. Choose the minute of the day
you want the generator to exercise then hit the “OK”
button.
SELECT AM/PM: Use the left of right arrow to toggle
between AM and PM. Once chosen, hit the “OK”
button.
NOTICE During the weekly exercise cycle, the generator will
run for 20 minutes, but it will not supply power to the home.
During the exercise cycle, the in-home monitor will continue
blinking the GENERATOR READY green LED.
If you want to change the day and time the unit exercises,
simply perform the procedure again.
To turn off the generator exercise cycle, go to the OFF
selection within the day of the week menu and press OK. The
display will then scroll: EXERCISE CYCLE OFF.
Maintenance
The generator warranty does not cover items that have been
subjected to operator abuse or neglect. To receive full value
from the warranty, the operator must maintain the system as
instructed in the Maintenance section.
Servicing the System
Before performing any generator maintenance, always
perform the following steps:
1. Set generator’s circuit breaker to its OFF position.
2. Set control panel system switch to OFF.
3. Remove 15 Amp fuse from control panel.
4. Utility voltage is present at generator control panel.
Disconnect power before servicing control panel by
removing the fuses from the transfer switch.
5. After all servicing has been completed, reinstall fuses in
transfer switch, replace 15 Amp fuse in control panel,
set system switch and circuit breaker ON and reset
exercise timer. See Setting Exercise Timer.
Service Code Detection System
The generator may have to run for long periods of time with
no operator present. For that reason, the system is equipped
with sensors that automatically shut down the generator in
the event of potentially damaging conditions, such as low oil
pressure, high temperature, over speed, and other conditions.
The generator’s control board shows service code
descriptions scrolling across the digital display. The service
code descriptions are listed below:
• Low Battery Voltage
• Low Oil Pressure
• Under Voltage
• Over Voltage
• Engine Does Not Start
• Low Frequency
• Engine Overspeed
• High Oil Temperature
• Transfer Switch Service code
• No Wireless Communication (Optional)
• Battery Charge Circuit
Reset Service code Detection System
The operator must reset the service code detection system
each time it activates. To do so, press the control board OFF
button for 5 seconds. Once the display turns off, leave it off
for at least 30 seconds. Remedy the service code condition,
then return the home generator to service by pressing and
holding the control board AUTO button and installing the 15
Amp fuse (if removed).