Installation Instructions
INSTALLATION (cont.}
| INSTALL THE OUTDOOR UNIT
Install the connection tube
i. Align the center of the tubing flare with the
relevant valve.
2. Screw in the flare nut by hand and then tighten
the nut with spanner and torque wrench. See
the table below for the correct torque.
3. Connecting tube specifications are shown
below:
10,000/14,00020,000
Spedficetions BTU Units BTU Units
Design Length 20ft. 26.2 ft.
ExtraRefrigerant Charge 0.16 oz./ft. 0.54 oz./ft.
PerFt.AboveDesignLength
Outer Diameter Liquid Pipe 1/4" 3/8"
Outer Diameter Gas Pipe 1/2" 5/8"
Max.Distance Height 33 ft. 33 ft.
Max. Distance Length 68 ft. 98 ft.
NOTE: Exceeding tightening torque will damage
the copper tubing.
Tightening torque table
Tubing OD
1/4"
3/8"
1/2"
5/8"
Tighteningtorque(in./Ib.)
140-170
270-310
440-480
530-570
Flarenut
Joint
Spanner
uewrench
NOTE: To prevent wind and pest infiltration,
seal holes around the tubing and wiring with
the supplied sealer.
I-_ PURGE THE AIR AND
TEST FOR LEAKAGE
,
2.
3.
,
5.
Install the connecting tubes of the
indoor/outdoor unit.
DO NOT OPEN THE GAS VALVES UNTIL THE
EVACUATION PROCESSIS COMPLETE.
Remove the gas line service port cap and
connect the gas valves of the vacuum gauge,
vacuum pump and outdoor unit.
NOTE: Connect bg using a 1/4" Female x
1/2" Male Adapter Access Fitting (obtain Iocallg).
Start the vacuum pump. (Running time should
be more than 15 minutes.)
Check the vacuum with the vacuum gauge. The
gauge should read -30 in. Hg. After evacuation,
fulls close the handle on the manifold valve
(on the vacuum pump device). Then stop the
vacuum pump and disconnect it.
6. The pressure should be kept for 1-2 minutes
to confirm that the reading of the vacuum
gauge does not change. The pressure should
be-30 in. Hg.
7. Remove the vacuum line and replace the service
port cap.
8. Remove both the liquid and gas valve caps.
9. Open the gas and liquid valve entirelg, using
the 5 mm Allen wrench. If this is not done, the
performance will be reduced, or an error will
OCCUr.
i0. Replace the caps and tighten securelg.
(
Cap
Liquid_hp_
Gas tube
Vacuum gauge
Vacuum pump
15