Auxiliary controls on your Zoneline
$X[LOLDU\&RQWUROV³7HUPLQDO&RQQHFWLRQV
The auxiliary control terminal connects are located 
behind the room cover beneath the access cover.
1
  Turn off and unplug the unit.
2
  Remove the room cover. See the To Remove the 
Room Cover section.
3
  To make wiring connections, insert the connectors 
into the appropriate terminals on the control box.
4
  After all desired connections have been made, 
replace the access cover and room cover.
The owner is responsible for making all connections and 
setting the appropriate AUX SET mode. 
NOTICE:
Improper wiring may damage the Zoneline electronics. 
No common busing is permitted. Damage or erratic 
operation may result. A separate wire pair must be run 
from each separate controlling switch to each individual 
Zoneline.
10
This electric heat option functions only on the AZ65 model. 
When this option is ON “ ,” heat pump operation 
is locked out, causing the unit to provide only electric 
resistance heat.
To set All-Electric Heat option, press MODE until an 8 
appears in the first digit of the display. Press the + or - pad 
to set this switch to OFF “ “ or ON “ .” This is shown in 
the second digit of the display. 
Press AUX SET to lock in your selection and exit AUX SET 
mode, or press MODE to continue setting other functions.
The default setting for Mode 8 is OFF.
When Heat Boost is ON and outside temperatures 
are between 25ºF and 46ºF, supplementary electric 
heat to the heat pump operation to help maintain a 
consistent, comfortable room temperature.
To set Heat Boost, press MODE until a 9 appears in the 
first digit of the display. Press the + or - pad to set this 
switch to OFF “ “ or ON “ .” This is shown in the 
second digit of the display. Press AUX SET to lock in 
your selection and exit AUX SET mode. 
The default setting for Mode 9 is OFF.
All-Electric Heat (AZ65 only)
MODE 8
Heat Boost (AZ65 only)
MODE 9
All-Electric 
Heat OFF
All-Electric 
Heat ON
Heat Boost OFF
Heat Boost ON
Red 
Aux Set 
Button