ELECTRICAL SUBBASE 
CONNECTION
   Power cords may include an arc fault interruption 
or a leakage current detection interruption device. 
A test and reset button is provided on the plug case 
or the inline case. The device should be tested on 
a periodic basis by first pressing the TEST button 
and then the RESET button. If the TEST button does 
not trip or if the RESET button will not stay engaged, 
discontinue use of the Zoneline and contact a 
qualified service technician.
Depending on application, a power supply kit with LCDI 
must be used to supply power to the Zoneline unit. The 
appropriate kit is determined by the voltage, the means of 
electrical connection and the amperage of the branch 
circuit.
Connections of 208 or 230-volt circuits may be with a 
power supply kit or a junction box kit. 
All wiring, including installation of the receptacle, 
must be in accordance with the NEC and local codes, 
ordinances and regulations. Codes require the use of 
an arc fault or leakage current detection device on the 
power cord except direct connect. Be sure to select the 
correct cord for your installation.
  Branch Circuit and  Proper GE Power Cord 
  Unit Amperage Rating  with LCDI Device
 15  RAK315P
 20  RAK320P
 30  RAK330P*
230/208 VOLT ELECTRICAL CONNECTION OPTIONS
POWER 
CORD CONNECTION
DIRECT CONNECTION
   Order the following Kit for 230/208-volt direct 
connection as required:
 Review installation instructions provided with power 
cord or direct connect kits for detailed assembly 
instructions. 
If using a sub-base connection, the RAK4002C Junction 
Box is also necessary for a complete installation.
  Branch Circuit and  Proper GE 
  Unit Amperage Rating  Subbase Kit
 15  RAK204D15PA
 20  RAK204D20PA
 30  RAK204D30PA
Tandem
15 Amp
230/208 volt receptacle configuration
Perpendicular
20 Amp
Large Tandem
30 Amp
Branch Circuit and 
Unit Amperage Rating
Power 
Supply Kit
15 RAK315D
20 RAK320D
30 RAK330D
Power supply kit
(Appearance may vary)
230/208-volt models may be installed using one 
of the following electrical subbases:
Electrical subbases provide an enclosure for direct 
connection or enclosed receptacles. The subbase kit 
includes the power cord.
The instructions provided with the selected subbase kit 
must be carefully followed. It is the responsibility of the 
installer to ensure the connection of components is done 
in accordance with these instructions and all electrical 
codes. 
If using a sub-base connection, the RAK4002C Junction 
Box is also necessary for a complete installation.
16