AZ45 SERIES | coolinG & electric heat
230/208v Models
AZ45E09DBM AZ45E12DBM
Cooling BTUh 9,100/9,100 11,800/11,700
EER
(
BTUh/Watt) 11.5/11.5 11.7/11.7
Listed by
Underwriters
Laboratories
ZONELINE PTAC WITH MAKEUP AIR
coMMon speciFications
DEhuMiDificAtion
RH% Operation >=55%, At >50°F outdoor temperature
Dehumidification rate* 5 - 6 pints/24 hrs
MAkEup Air fAn
Watts 15
Amps 0.1
Motors 2 DC fan motors, in addition to PTAC fan motors
CFM Range 25-50 CFM at zero static pressure
CFM Configuration 6 stages pre-programmed: 25/30/35/40/45/50
coMprEssor
Voltage 230/208 265
Refrigerant 134A 134A
Watts 205 205
Rated Load Amps 1.15/1.05 0.8
Added operational load 1.2A 1.0A
Psig (high) 220 220
Psig (low) 75 103
MiscEllAnEous
Occupancy Sensing Compatible YES**
CFM configuration control Adjustable via AUX setting on control panel
PTAC AHRI Certification YES
PTAC UL and cUL certification YES
PTAC ASHRAE 90.2013 YES
*Dependant on CFM.
**RAKCDC accessory required.
For More inForMation | 1-888-231-2548 zoneline@geappliances.com Zoneline.com
AZ65 SERIES | heat puMp
230/208v Models
aZ65h07dbM aZ65h09dbM aZ65h12dbM
Cooling BTUh 7,000/7,000 9,200/9,100 11,400/11,500
Heating BTUh 6,200/6,100 8,000/7,900 10,200/10,000
EER 12.5/12.5 11.3/11.3 11.2/11.2
COP 4.0/4.0 3.3/3.3 3.5/3.5
265v Models
aZ65h07ebM aZ65h09ebM aZ65h12ebM
Cooling BTUh 6,900 9,200 11,700
Heating BTUh 6,000 8,100 10,400
EER 12.5 11.5 11.4
COP 3.9 3.6 3.5
desiGn considerations:
To avoid bringing salt/corrosive air into
living space, Makeup Air Systems are not
recommended for installations within
two miles of coastal areas
The Makeup Air Module will increase
room load requirements for both heating
and cooling.
Consult with your architect or engineer to
ensure proper sizing of the PTAC/PTHP
unit to accommodate this additional load.
Due to additional heating and cooling
load, energy costs of the room will
increase with the use of makeup air.
Because makeup air increases room
BTU load requirements and requires
additional PTAC cooling or heating,
the building's electrical needs may
be impacted.
Install Makeup Air Models with wall
thermostats
With the additional dehumidication of
outside air, additional condensate will be
generated and therefore an internal or
external piped drain line is recommended.
Consider noise levels before installing
around areas with high trac.
It is the architect's/engineer's/
contractor's/customer's responsibility
to verify all state and local codes to ensure
product meets local code requirements.
Ducted installations are not available with
makeup air models.
GE ZONELINE | quietest ptac in the industry*
Each Zoneline Makeup Air unit has all the leading features of the base Zoneline unit—composite base pan, mastic sound barrier,
auto dimming LED controls and many others. The GE Zoneline with Makeup Air is also covered by the same warranty as all other
Zoneline models. Reference the GE Zoneline Architects & Engineering Manual for full system specifications.