Spec Sheet

AZ91H09D2E/D3E/D5E
GE Zoneline
®
Heat Pump Single Package
Vertical Air Conditioner, 230/208 Volt
For answers to your Monogram, GE Café
Series, GE Profile
Series or
GE Appliances product questions, visit our website at geappliances.com
or call GE Answer Center
®
Service, 800.626.2000.
Specification Revised 9/19
DIMENSIONS AND INSTALLATION INFORMATION (IN INCHES)
23-1/8
23-1/8
32-1/4
230/208 VOLT AZ91H09D2E AZ91H09D3E AZ91H09D5E
Heater KW 2.5/2.05 3.4/2.78 5 /4.09
Min. Circuit Amps 15 20 30
Recommended
Protective Device
15 Amp Time Delay
Fuse or Breaker
20 Amp Time Delay
Fuse or Breaker
30 Amp Time Delay
Fuse or Breaker
MINIMUM CLEARANCES:
FRONT-ACCESS CLOSETS
FRONT
- Allow 4 inches in front of unit.
SIDES
- Allow 3 inches on each side of unit.
OPTIONAL PLATFORM
- Field-supplied, refer to installation instructions.
- Platform height must coordinate with the height of the thru wall plenum.
SIDE-ACCESS CLOSETS
- Allow 12" in front of unit, 3-6" minimum on access side and 3" on opposite side.
- 30" opening on side with full manpower is optimal.
- Provide extra wiring to allow for power and thermostat connection prior to installation.