Operating Guide

WattStation Wall Mount User Manual
4 GE Energy ©2011 GE Company All Right Reserved
Torque Specification Table: (needs to be updated with info from Pradeep)
COMPONENT TORQUE VALUE TOLERANCE
M5 x 0.8 screw 30 in-lb +/- 2 in-lb
#12 thread-cutting screw 30 in-lb +/- 2 in-lb
10-32 UNF screw 35 in-lb +/- 5 in-lb
6-32 UNC screw 12 in-lb +/- 2 in-lb
Fuse block lugs 45 in-lb +/- 2 in-lb
Field wiring lugs 50 in-lb +/- 2 in-lb
Din-rail mounted terminal block lugs 12 in-lb +/- 2 in-lb
Contactor lugs 50 in-lb +/- 2 in-lb
Ground bar lugs 35 in-lb +/- 2 in-lb
3/4" cable strain relief fitting Hand-Tight + 1/4 turn N/A
2.2 Plug-in Version
2.2.1 Before Installation
• Ensure that a dedicated circuit, capable of supplying 30A at 208-240 VAC,
is available
• Power feed must have a centrally grounded neutral in order for WattStation to
function correctly.
• Wall receptacle must be a NEMA 6-50 outlet. A recommended 40A upstream
circuit breaker, located either in a panelboard or load center, should be used
• Distance between the wall power receptacle and WattStation mounting should
be less than one (1) foot
• Wall power receptacle with a weatherproof locking cover is recommended
• Recommended mounting hardware for wood studs are 3/8" x 2" hex head lag
bolts. Recommended mounting hardware for concrete walls are 3/8" x 1-3/4"
concrete hex screws or 3/8" x 1-7/8" concrete anchors
WARNING: Danger of electrical shock or injury. Turn
OFF power at the panelboard or load center before
working inside the equipment or removing any
component.
Do not remove circuit protective
devices or any other component until the power is
turned OFF.
WattStation should be installed only by a licensed contractor,
and/or a licensed electrician in accordance with all applicable
state, local and national electrical codes and standards.