ELECTRICAL CONNECTIONS
A separate branch circuit with copper conductors, 
overcurrent protective device and suitable disconnecting 
means must be provided by a qualified electrician. 
All wiring must conform to local codes or latest edition of 
National Electrical Code ANSI/NFPA 70.
7KHZDWHUKHDWHULVFRPSOHWHO\ZLUHGWRWKHMXQFWLRQER[DW
WKHWRSRIWKHZDWHUKHDWHU$QRSHQLQJIRU´HOHFWULFDO
fitting is provided for field wiring connections.
The voltage requirements and wattage load for the water 
heater are specified on the rating label on the front of the 
water heater.
The branch circuit wiring should include 
either:
1. Metallic conduit or metallic sheathed cable 
approved for use as a grounding conductor and 
installed with fittings approved for the purpose.
2. Nonmetallic sheathed cable, metallic conduit or 
metallic sheathed cable not approved for use 
as a ground conductor shall include a separate 
conductor for grounding. It should be attached to 
the ground terminals of the water heater and the 
HOHFWULFDOGLVWULEXWLRQER[
To connect power to the water heater:
1. Turn the power off.
5HPRYHWKHVFUHZVFUHZVKROGLQJWKHMXQFWLRQER[
top cover.
3. Install L1 to L1, L2 to L2 and ground to the green 
ground wire connected to the bottom of the junction 
ER[
NOTE: Install electric connections according to local 
codes or latest edition of National Electrical Code 
ANSI/NFPA 70.
WARNING
 Proper ground connection is 
essential. The presence of water in the piping and 
water heater does not provide sufficient conduction 
for a ground. Nonmetallic piping, dielectric unions, 
flexible connectors, etc., can cause the water heater 
to be electrically isolated. Do not disconnect factory 
ground.
240V
-XQFWLRQER[
cover
Junction 
ER[
Factory Ground
House Ground 
(Green)
L2 
(Red)
L1 
(Black)
The manufacturer’s warranty does not cover any damage 
or defect caused by installation, attachment or use of any 
type of energy-saving or other unapproved devices (other 
than those authorized by the manufacturer) into, onto or in 
conjunction with the water heater. The use of unauthorized 
energy-saving devices may shorten the life of the water 
heater and may endanger life and property. 
The manufacturer disclaims any responsibility for such 
loss or injury resulting from the use of such unauthorized 
devices.
,IORFDOFRGHVUHTXLUHH[WHUQDODSSOLFDWLRQRILQVXODWLRQ
blanket kits, the manufacturer’s instructions included with 
the kit must be carefully followed.
Application of any external insulation, blankets or water 
pipe insulation to this water heater will require careful 
attention to the following:
• Do not cover the temperature and pressure-relief valve.
• Do not cover access panels to the heating elements.
'RQRWFRYHUWKHHOHFWULFDOMXQFWLRQER[RIWKH 
water heater.
• Do not cover the operating or warning labels attached 
to the water heater or attempt to relocate them on the 
H[WHULRURIWKHLQVXODWLRQEODQNHW
• Do not block the air inlet/outlets in the top covers or rear 
of the unit.
NOTE: This guide recommends minimum branch 
circuit sizing based on the National Electric Code. 
5HIHUWRZLULQJGLDJUDPVLQWKLVPDQXDOIRU¿HOGZLULQJ
connections.
BRANCH CIRCUIT SIZING GUIDE
  Total Water  Recommended Over-Current Protection  
  Heater Wattage  (fuse or circuit breaker amperage rating)
     208V 240V 277V 480V
  3,000   20 20 15 15
  4,000   25 25 20 15
   4,500   30 25 25 15
  5,000   30 30 25 15
  5,500   35 30 25 15
  6,000   40 35 30 20
  8,000   50 45 40 25
  9,000   – 50 45 25
 10,000    –  –  50  30
 11,000    –  –  50  30
 12,000    –  –   – 35
  Total Water  Copper Wire Size AWG Based  
  Heater Wattage  on N.E.C. Table 310-16 (167°F/75°C.)
     208V 240V 277V 480V
  3,000   12 12 14 14
  4,000   10 10 12 14
   4,500   10 10 10 14
  5,000   10 10 10 14
  5,500   8 10 10 14
 6,000    8  8  10  12
 8,000    8  8  8  10
 9,000    –  8  8  10
 10,000    –  –  8  10
 11,000    –  –  8  10
 12,000   – – – 8