Installation instructions

GEI-M1011A
VII. TROUBLE SHOOTING CHART
Affected Parts Difficulty What to Check
Windings Overheating
Calibration of measuring instrument
Excessive load
Unbalanced AC current
Improper or restricted ventilation
Excessive ambient temperature
Short circuited coil or windings
Dirty windings
Unbalanced voltage
Harmonics in Power Supply (Variable Frequency Control
Fan Broken
Bearings Overheating
Calibration of measuring instrument
Worn out or dirty oil or grease
Insufficient oil or grease
Misalignment
Excessive thrust or radial loading
Shaft currents
Improper end-play
Fan broken
Insufficient cooling water
Insufficient down thrust (on SRB)
Bearing Housing Oil Leaks
Incorrect grade of oil (type or viscosity)
Loose fittings
Cracked/porous casting
Over-filled
Water in oil
Motor Excessive Vibration
Unbalance
Misalignment
Improper or settled foundation
Non-uniform air gap
Rubbing parts
Bent shaft
Unbalanced stator current
Damaged bearings
Reed Critical Frequency
Incorrect end-play
Fan broken
Motor Failure to Start
Wrong transformer taps
Wrong connections
Open circuit
Excessive line drop (low voltage at motor)
Excessive load
Rotor rubs
Wrong direction of rotation
Insulation Low Insulation
Resistance or
Moisture, dirt, metal particles, oil, or other contaminants on
the insulated windings
Insulation Failure
Wrong voltage
Excessive temperature
Voltage surges/lightning
Mechanical damage
Excessive vibration with resultant mechanical damage
Single-phasing
19