Installation Guide

6
4-WIRE INSTALLATION
WARNING
The neutral wire of
the supply circuit must be connected to the
neutral terminal located in the lower center of
the terminal block. The power leads must be
connected to the lower left and the lower right
terminals of the terminal block. The grounding
lead must be connected to the frame of the
range with the ground plate and the green
ground screw.
FOR POWER CORD INSTALLATION
A. Remove the 3 lower terminal screws
from the terminal block. Remove the
ground screw and ground plate and retain
them. Cut and discard the ground strap.
DO NOT DISCARD ANY SCREWS.
B. Insert the one ground screw into the power cord
ground wire terminal ring, through the ground
plate and into the frame of the range.
C. Insert the 3 terminal screws (removed earlier)
through each power cord terminal ring and into
the lower terminals of the terminal block. Be
certain that the center wire (white/neutral) is
connected to the center lower position of the
terminal block. Tighten screws securely into the
terminal block.
FOR CONDUIT INSTALLATION
A. Loosen the 3 lower terminal screws on the
terminal block. Strip wire to exposed tip about
5/8” long.
B. Insert the center (white/neutral) wire tip through
the bottom center terminal block opening. On
certain models, the wire will need to be ins
erted through the ground strap opening and
then into the bottom center block opening.
Insert the two side bare wire tips into the lower
left and the lower right terminal block openings.
C. Tighten the screws until the wire is firmly
secured (35 to 50 inch-lbs.). Do not over-tighten
the screws.
NOTE: ALUMINUM WIRING: Aluminum building wire may be used but it must be rated for the
correct amperage and voltage.
Before–Power Cord and Conduit
Terminal
block
Neutral
terminal
Ground
strap
Ground strap
or
After–Conduit
Terminal
block
Ground
plate
(grounding
to range)
Wire
tips
Ground screw
Terminal
block
Neutral
terminal
Ground plate
(grounding to
range)
Ground
screw
After–Power Cord
5
3-WIRE INSTALLATION
WARNING
The neutral or ground wire of the power cord must be connected to the
neutral terminal located in the center of the terminal block and the ground strap must connect the
neutral terminal to the ground plate. The power leads must be connected to the lower left and the
lower right terminals of the terminal block.
DO NOT remove the ground strap connection.
FOR POWER CORD INSTALLATION
A. Remove the 3 lower terminal screws from the terminal block.
B. Insert the 3 terminal screws through each power cord terminal ring and into the lower terminals
of the terminal block. Be certain that the center wire (white/neutral) is connected to the center
lower position of the terminal block.
C. Tighten screws securely into the terminal block.
FOR CONDUIT INSTALLATION
A. Loosen the 3 lower terminal screws on the terminal block. Strip wire to expose tip about 5/8”
long.
B. Insert the center (white/neutral) wire tip through the bottom center terminal block opening. On
certain models, the wire will need to be inserted through the ground strap opening and then
into the bottom center block opening. Insert the two side bare wire tips into the lower left and
the lower right terminal block openings.
C. Tighten the screws until the wire is firmly secured (35 to 50 inch-lbs.). Do not over-tighten the
screws.
NOTE: ALUMINUM WIRING: Aluminum building wire may be used but it must be rated for the
correct amperage and voltage.
PROCEED TO STEP 7.
Wire tips
Terminal
block
Conduit
Ground strap
Terminal block
(appearance
may vary)
Neutral terminal
Power cord
Ground
plate
Power Cord