GE Consumer & Industrial Electrical Distribution Double-Throw Safety Switch, NAME 1 DEG-44153 Installation Instructions 30-400 Ampere Double-Throw Safety Switch General To comply with the National Electrical Code and Underwriters Laboratories, the safety switch must be installed in accordance with the information provided on the UL rating label on the inside of the equipment. Follow all local electrical codes and have work performed by a qualified electrical contractor and/or licensed electrician only.
8. Wire Phase A, B and C of Line 2 as shown. Refer to rating label inside switch for Line lug tightening torque. Wire Line 2 only in the direction indicated by the arrow, l Line 2 terminals 9, Re-check all electrical connections. Ensure that all electrical connections are tightened to the proper torque before energizing the suety switch. 10. Close door. Close the door and ensure that latch A [see Step 2}is engaged. How to use the interlock defeat feature WARNING: Hazard of electrical shock or burn.
GE Consumer & Industrial Electrical Distribution Double-Throw Safety Switch, NAME 3R DEG-44154 Installation Instructions 30-400 Ampere Double-Throw Suety Switch General To comply with the National Electrical Code and Underwriters Laboratories, the safety switch must be instated in accordance with the information provided on the UL rating label on the inside of the equipment. Follow all local electrical codes and have work performed by a qualified electrical contractor and/or licensed electrician only.
8. Wire phase A, B, and C of Line 1 as shown. Refer to rating libel inside switch for line lug tightening torque. Pull Lionel wires into the switch in the direction indicated by the arrows. e € B 878 Wire three phases Line 2 as shown. Refer to rating label inside equipment for proper tightening torque. Wire Line 2 only in the direction indicated by the arrow. l Line 2 terminals B Emd 10.