Technical Specifications

103
Pressure Frame
Configuration Services
Pressure Frame
Pressure Units This is the unit code in TB.SPRING_RANGE parameter that
affects output pressure unit code as well. It has no effect, how-
ever, in controlling function.
Upper Range
(EU100)
This is the supply pressure in engineering units specified in the
TB .SPRING_RANGE parameter. It is for information only and
has no effect on control.
Lower Range (EU0) This is EU100 of TB .SPRING_RANGE parameter for upper
end engineering unit value.
Supply Pressure This is EU0 of TB .SPRING_RANGE parameter for lower end
engineering unit value.
Others Frame
Bumpless Transfer When this option is selected, returning from manual to normal
operation state is deferred until the current valve position and
the position Set Point match. This is to assure the smooth valve
position transition when switching the operation state to avoid a
process disturbance. For most Foundation Fieldbus installa-
tions the initialization function built into the function blocks han-
dles bumpless transfer. Leave the box unchecked unless there
is a special requirement.
Display Language This is the display language setting specific to the language
locale. It is currently unused.
Temperature Units ° C or ° F. This is the temperature unit used in the device that
has thermal settings.
Calibration Date Last day this device was calibrated, enter automatically.
Calibration Person ID of the technician performing the calibration.
Calibration Location The factory, or other location, where calibration was performed.
Servo Tuning Info. Displays whether the device was tuned manually or automati-
cally.