Technical Specifications

ValVueFF Software Interface to FVP
208
GE Energy
Online Diagnostics
The results of online diagnostics are shown in the parameter XD_ERROR and explained
in Table 17. Other diagnostic messages applicable to internal circuits, memory failure for
example, are reported in the Resource Block.
102 Fifty percent angle error
103 Linear adjust error
120
Offset measurement failed
error
121 Gain measurement failed error
122
Response speed
measurement failed error
123
Hysteresis measurement
failed error
255 In operation (executing)
Table 17 Error Messages
XD Error Message Possible Cause
0 No error
100
Cycle count limit exceeded TOTAL_CYCLE_COUNT exceeded
CYCLE_CONT_LIM
101 Travel limit exceeded TOTAL_TRAVEL exceeded TRAVEL_LIM
102
Total open limit exceeded TOTAL_OPEN_TIME exceeded
OPEN_TIME_LIM
103
Total close limit exceeded TOTAL_CLOSE_TIME exceeded
CLOSE_TIME_LIM
104
Total near close limit
exceeded
TOTAL_NEAR_CLOSE_TIME exceeded
NEAR_CLOSE_TIME_LIM
110 Temperature out of range
111 Pressure sensor out of range
112 Position sensor out of range
113
Deviation warning Exceed the first DEVIATION_TIME_TH[1]
timer with DEVIATION_LIM
Table 16 Auto Tune Results (Continued)
Reference Message Possible Cause