User Manual
8
 D
 GB
 F
 E
96031-02.2015-DGbF
3 |  Areas of application
 ATTENTION!     Compressor operation is possible within the operating limits 
shown in the diagrams. Thresholds should not be selected as 
design or continuous operation points.
           - Max. permissible ambient temperature 45°C 
        - Max. permissible discharge end temperature 160°C.
    -Max.permissibleswitchingfrequency12x/h.
        - A minimum running time of 3 min. steady-state condition 
 (continuous operation) must be achieved.
 Thecompressorsarelledatthefactorywiththefollowingoiltype:
GEABockC85E(onlythisoilmaybeused).
 3.1  Refrigerants
•  CO
2
: R744
3.2  Oil  charge
3.3  Limits of application
Max. permissible operating 
pressure (LP/HP)
1)
: 100/150 bar
The oil level must be in the 
visible part of the sight 
glass; damage to the com-
pressor is possible if over-
filled or underfilled!
max. oil level
min. oil level
ATTENTION!
Fig. 4
1) 
LP = Low pressure
 HP = High pressure
Fig. 5
t
o
  Evaporation temperature (°C)
∆t
oh 
  Suction gas superheat (K)
p
o 
Suction pressure (bar)
p
v2
  Discharge end pressure (bar)
1
1
HAX2/130-4 CO
2 
T
Applications limit
 Unlimited   
application range