7.1 Preparation
7.2 Worktobecarriedout
7| Maintenance
In order to guarantee optimum operational reliability and service life of the compressor, we   recommend 
carryingoutservicingandinspectionworkatregularintervals:
  Oil change: 
   -  not mandatory for factory-produced series systems.
 - foreldinstallationsorwhenoperatingneartheapplicationlimit:forthersttimeafter100
to 200 operating hours, then approx. every 3 years or 10,000 - 12,000 operating hours. 
Dispose of used oil according to the regulations; observe national regulations.
  Annual checks: Oil level, leak tightness, running noises, pressures, temperatures, function of 
 auxiliary devices such as oil sump heater, pressure switch.
WARNING!  Beforestartinganyworkonthecompressor:
      Switch off the compressor and secure it to prevent a restart.
      Relieve compressor of system pressure.
     Preventairfrominltratingthesystem!
     After maintenance has been performed:
      Connect safety switch.
      Evacuate compressor.
  Releaseswitch-onlock.
6.8  Connection of oil level regulator
Theconnection"O"isprovidedforinstallinganoillevelregulator.Acorrespondingadaptermustbe
obtained from the trade.
6| Commissioning 
OnlyusegenuineGEABockspareparts!
7.3  Spare parts recommendation
HG22P / ...
125-4(S) 160-4(S) 190-4(S)
Designation
Ref. No. Ref. No. Ref. No.
Set of gaskets 80313
Valve plate kit 80305 80306
Oil pump kit 08324